Measured value / Parameter

Parameter name for Speedwire/Webconnect

Parameter name for RS485

Description

Read level

Displayed group in the communication product

Value range / Unit / Set values

Default value

Step size

Write level

Grid Guard

Object name

Measured value

Absorption phase active

‒

–

Installer

Battery > Battery > Absorption phase active

  • Yes: Absorption phase active
  • No: Absorption phase not active
  • Information not available

‒

‒

‒

‒

Bat.AbsPhsAct

Measured value

Control of battery charging via communication available

‒

‒

Installer

Battery > Battery > Control charging via communication available

  • Yes
  • No
  • Information not available

‒

‒

‒

‒

Bat.ChaCtlComAval

Parameter

Manual equalization charge

‒

Manual equalization charge

User

Battery > Battery > Operation > Manual equalization charge

  • Stop
  • Wait
  • Start

‒

‒

User

‒

Bat.Operation.EqChaMan

Measured value

Battery oper. status

‒

‒

User

Battery > Battery > Operating status

  • Charge battery
  • Discharge battery
  • Information not available

‒

‒

‒

‒

Bat.OpStt

Parameter

Battery type

‒

–

User

Battery > Battery > Type

  • Valve Regulated Lead Acid battery (VRLA)
  • Flooded lead acid batt. (FLA)
  • Lithium-Ion (Li-Ion)

‒

‒

Installer

‒

Bat.Typ

Parameter

Most productive month for battery usage range

‒

–

Installer

Battery > Areas of application > Most profitable month

  • June profitable
  • December profitable

‒

‒

Installer

‒

BatUsDm.MaxYldMth

Parameter

Season operation active

‒

Automatic adjustment of the battery depth of discharge: In seasons with fewer hours of sunlight, the electric discharge of the battery will be lower.

Installer

Battery > Areas of application > Season operation active

  • Yes: Enable
  • No: Disable

‒

‒

Installer

‒

BatUsDm.SanModAct

Measured value

Status battery application area

‒

In systems for increased self-consumption and in battery-backup systems, this parameter shows in which range the state of charge of the battery is currently in.

Installer

Battery > Areas of application > Status

  • Own consumption area: Range for increased self-consumption
  • State of charge conservation area: Range for maintenance of the battery state of charge
  • Backup power area: Range for the battery backup system function
  • Deep discharge protection area: Range for protection against deep discharge
  • Deep discharge protection area: Range for protection in the event deep discharge
  • Information not available

‒

‒

‒

‒

BatUsDm.Stt

Parameter

Automatic equalization charge

‒

–

Installer

Battery > Charge > Automatic equalization charge

  • Off: Disable
  • On: Enable

‒

‒

Installer

‒

Cha.EqChaAuto

Parameter

BMS operating mode

‒

‒

Installer

Battery > Battery management system > Operating condition

  • Off: Disable
  • On: Enable
  • Charge battery
  • Discharge battery
  • Presetting

‒

‒

InstallerDevice Control ObjectCmpBMS.OpMod

Parameter

Language of the user interface

CntrySet.Lang

‒

User

Device > Country settings > Language

  • Deutsch
  • English
  • Italiano
  • Español
  • Français
  • Ελληνικά
  • 한국어
  • Česky
  • Português
  • Nederlands
  • Polski
  • ภาษาไทย

English

‒

User

‒

CntrySettings.Lang

Parameter

Fan test

CoolSys.FanTst

‒

Installer

Device > Cooling system > Fan test

  • Off: Disable
  • On: Enable
  • Automatic

‒

‒

Installer

‒

Coolsys.FanTst

Parameter

Operating mode of the device update

‒

Type of firmware update

User

System communication > Device update > Operating mode

  • Automatic update
  • Time-controlled

‒

‒

User

‒

DevUpd.OpMode

Parameter

Time zone

‒

‒

User

Device > Time settings > Time zone

  • (UTC-AUTO) Automatic via SMA protocol

(UTC-AUTO) Automatic via SMA protocol

‒

User

‒

DtTm.TmZn

Parameter

Standard/Daylight saving time conversion on

‒

‒

User

Device > Time settings > Standard/Daylight Saving Time conversion on

  • Yes
  • No

Yes

‒

User

‒

DtTm.DlSvIsOn

Parameter

Current time is daylight savings time

‒

‒

User

Device > Time settings > Current time is daylight savings time

  • Yes
  • No

No

‒

User

‒

DtTm.SetDlSvTm

Parameter

Automatic time synchronization

‒

‒

User

Device > Time settings > Automatic time synchronization

  • Yes
  • No

Yes

‒

User

‒

DtTm.TmSynIsOn

Parameter

Automatic generator start

‒

Automatic generator start (e.g., via state-of-charge-dependent generator request)

User

Generator > Generator > Automatic start

  • Off: Disable
  • On: Enable

‒

‒

User

‒

Gn.AutoStr

Parameter

Manual generator control

‒

–

User

Generator > Generator > Manual control

  • Stop: Stop
  • Start: Start
  • Manual one hour
  • Automatic generator start

‒

‒

User

‒

Gn.ManCtl

Parameter

Acknowledge generator errors

‒

–

User

Generator > Generator > Operation > Acknowledge fault

  • Acknowledge fault

‒

‒

User

‒

Gn.Operation.Ackn

Measured value

Generator status

‒

–

User

Generator > Generator > Operating status

  • Off: Deactivated generator operation
  • Fault: –
  • Initialization: Re-detection of the generator
  • Ready: Waiting for request
  • Warming: Warming up
  • Synchronization: Start-up
  • Activated: Operation
  • Resynchronization: Restart
  • Generator separation: –
  • Slow down: Cooling down
  • Bolted: Locked after operation
  • Blocked after error: –
  • Information not available

‒

‒

‒

‒

Gn.OpStt

Parameter

Generator request

‒

–

User

Generator > Generator > Request

  • Automatic generator start
  • Manual generator control

‒

‒

Installer

‒

Gn.DmdMod

Parameter

Generator request with set charge type

‒

–

User

Generator > Generator request via charge type > Charge type

  • Off
  • Full and equalization charge
  • Full charge
  • Equalization charge

‒

‒

Installer

‒

GnDmdChaMod.ChaMod

Parameter

Reaction to digital input of generator request

‒

–

User

Generator > Generator request via digital input > Reaction to digital input

  • Off
  • On

‒

‒

Installer

‒

GnDmdDigIn.DigInRea

Parameter

Time-controlled generator operation

‒

–

User

Generator > Time-controlled generator operation > Activated

  • Yes
  • No

‒

‒

Installer

‒

GnDmdTm.IsOn

Parameter

Repeat cycle of time-controlled generator op.

‒

–

User

Generator > Time-controlled generator operation > Repeat cycle

  • daily
  • Once
  • Weekly

‒

‒

Installer

‒

GnDmdTm.RptCyc

Parameter

Generator request via power on

‒

–

User

Generator > Generator request via power > Activated

  • Yes
  • No

‒

‒

Installer

‒

GnDmdW.IsOn

Parameter

Country standard set

Cntry

‒

User

Grid Monitoring > Grid monitoring > Country standard

  • Special setting
  • Island mode
  • VDE-AR-N4105
  • VDE-AR-N4105-MC
  • Adjusted-MC
  • Information not available

‒

‒

‒

‒

GridGuard.Cntry

Parameter

Underlying country standard

‒

‒

Installer

Grid Monitoring > Grid monitoring > Underlying country standard

  • Island mode
  • VDE-AR-N4105
  • VDE-AR-N4105-MC
  • Adjusted-MC
  • AS4777.2_2015

‒

‒

‒

‒

GridGuard.CntryBas

Parameter

Set country standard

CntrySet

‒

Installer

Grid Monitoring > Grid monitoring > Set country standard

    ‒

‒

‒

Installer

‒

Country

Parameter

Voltage increase protection enabled

‒

‒

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Enable voltage increase protection

  • Yes
  • No

‒

‒

Installer

‒

GridGuard.Cntry.VolCtl.RproEna

Parameter

Design of the generation plant

‒

‒

Installer

System and device control > Grid monitoring > Design of the generation plant

  • Symmetric
  • Asymmetric

Symmetric

‒

Installer

‒

GridGuard.EzaTyp

Parameter

Nominal voltage and frequency

‒

‒

Installer

Device > Inverter > Nominal voltage and frequency

  • 230V_50Hz
  • 220V_60Hz

‒

‒

Installer

‒

Inverter.AcVHzTyp

Parameter

Device address

‒

‒

Installer

Device > Inverter > Address

  • Slave 1
  • Slave 2
  • Master

‒

‒

‒

‒

Inverter.Addr

Parameter

AST type

‒

‒

Installer

Device > Inverter > AST type

  • SIAST50-48-12
  • SIAST50-48S-12

‒

‒

Installer

‒

Inverter.ASTType

Parameter

Cluster in the multi-cluster

‒

Cluster type is adjustable in the installation assistant

Installer

Device > Inverter > Cluster > Cluster type in multi-cluster

  • -------
  • Main-cluster
  • Extension cluster

‒

‒

Installer

‒

Inverter.Clt.CltMod

Parameter

Phase assignment device 1

‒

‒

Installer

AC Side > Inverter > Cluster > Phase assignment device 1

  • Line conductor L2
  • Line conductor L3

‒

‒

Installer

‒

Inverter.Clt.PhsDev1

Parameter

Phase assignment device 2

‒

‒

Installer

AC Side > Inverter > Cluster > Phase assignment device 2

  • Line conductor L2
  • Line conductor L3

‒

‒

Installer

‒

Inverter.Clt.PhsDev2

Parameter

Cluster system

‒

‒

Installer

Device > Inverter > Cluster > System

  • Single-cluster
  • Multi-cluster

‒

‒

Installer

‒

Inverter.Clt.Sys

Parameter

Cluster configuration

‒

‒

Installer

Device > Inverter > Cluster > Type

  • Single phase
  • Three-phase

‒

‒

Installer

‒

Inverter.Clt.Typ

Parameter

Source of ref. meas. for reactive/active power reduction

‒

Set the default of the measuring point that is being controlled during feed-in operation.

Installer

System and device control > Inverter > Configuration of system control via communication > Source of ref. meas. for reactive/active power reduction

  • Inverter
  • MC box

‒

‒

Installer

‒

Inverter.CtlComCfg.CtlMsSrc

Parameter

Phased reactive/act. power specification

‒

‒

Installer

System and device control > Inverter > Configuration of system control via communication > Phased reactive/act. power specification

  • Off
  • On

‒

‒

Installer

‒

Inverter.CtlComCfg.PhsCtlMod

Parameter

Functions for grid/offgrid operation

‒

‒

Installer

Device > Inverter > Functions for grid/offgrid operation

  • Functions for grid operation
  • Functions for offgrid operation

‒

‒

Installer

‒

Inverter.GriOffOpMod

Parameter

Phase assignment

Inv.OutPhsSet

Line conductor to which the Sunny Island is connected.

Installer

AC Side > Inverter > Phase assignment

  • Line conductor L1
  • Line conductor L2
  • Line conductor L3

‒

‒

Installer

‒

Inverter.OutPhs

Parameter

System performance

‒

‒

Installer

Device > Inverter > System performance

  • Internal consumption only
  • Backup only
  • Intern. consumption and backup

‒

‒

Installer

‒

Inverter.SysFncSel

Parameter

cosPhi excit.type, cosPhi config., direct spec.

PF-PFExt

–

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi, direct specification > Excitation type of cosPhi

  • Overexcited: Lagging
  • Underexcited: Leading

‒

‒

Installer

‒

Inverter.VArModCfg.PFCnstCfg.PFExt

Parameter

Excit. type at start point, cosPhi(P) char. conf.

PF-PFExtStr

–

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Excitation type at starting point

  • Overexcited: Lagging
  • Underexcited: Leading

‒

‒

Installer

‒

Inverter.VArModCfg.PFCtlWCfg.PFExtStr

Parameter

Excit. type at end point, cosPhi(P) char. config.

PF-PFExtStop

–

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Excitation type at end point

  • Overexcited: Lagging
  • Underexcited: Leading

‒

‒

Installer

‒

Inverter.VArModCfg.PFCtlWCfg.PFExtStop

Parameter

Operating mode of stat.V stab., stat.V stab. config.

Q-VArMod

–

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Operating mode of static voltage stabilization

  • Off: Disable
  • cosPhi, direct specific.: Constant displacement power factor cos φ
  • cosPhi(P) characteristic: Automatic adaptation of the displacement power factor according to the current active power

‒

‒

Installer

‒

Inverter.VArModCfg.VArMod

Parameter

Operating mode of active power reduction in case of overfrequency P(f)

P-WCtlHzMod

–

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Operating mode active power red., overfreq. P(f)

  • Off: Deactivation of the active power reduction
  • Linear gradient

‒

‒

Installer

‒

Inverter.WCtlHzModCfg.WCtlHzMod

Parameter

Activation of active power gradient for reconnection after grid fault

WGraReconEna

‒

Installer

System and device control > Inverter > Curr. active power grad., reconnection, grid fault

  • Off: Deactivation of the active power reduction
  • On

‒

‒

Installer

‒

Inverter.WGraReconEna

Parameter

Eff./reac. pow. contr. via comm.

‒

‒

Installer

System and device control > Inverter > Configuration of feed-in management > Configuration of active power mode of PV system ctrl > Act./reac. pow. contr. via comm.

  • Active
  • Inactive

‒

‒

InstallerDevice Control ObjectInverter.WModCfg.WCtlComCfg.WCtlComAct

Parameter

Operating mode of feed-in management

P-WMod

‒

Installer

System and device control > Inverter > Configuration of feed-in management > Operating mode Active power

  • Act. power lim. via PV system ctrl

‒

‒

Installer

‒

Inverter.WModCfg.WMod

Measured value

Battery maint. state of charge

‒

If full charge or equalization charge with PV energy has not ended after 24 hours, the parameter automatically switches to the status "Charge with solar- and grid current".

User

Battery > Maintenance > Full and equalization charge

  • Inactive: No full charge or equalization charge active.
  • Charge with solar power: If sufficient PV energy is available, full charge or equalization charge active.
  • Charge w. solar a. mains power: Full charge or equalization charge active, energy is drawn from the utility grid.
  • Information not available

‒

‒

‒

‒

Maint.FulEqCha

Parameter

Modbus TCP server on

‒

‒

User

External Communication > Modbus > TCP server > Activated

  • Yes
  • No

No

‒

Installer

‒

Mb.TcpSrv.IsOn

Parameter

Modbus UDP server on

‒

‒

User

External Communication > Modbus > UDP server > Activated

  • Yes
  • No

No

‒

Installer

‒

Mb.UdpSrv.IsOn

Measured value

Speedwire meter status

‒

‒

User

System communication > Measured values > Meter on Speedwire > Condition

  • Ok
  • No connection

‒

‒

‒

‒

Metering.MsSpdwr.Health

Parameter

Activation of communication test between clusters

‒

–

Installer

External Communication > Multi-cluster > Activation of communication test

  • Off: Disable
  • On: Enable

‒

‒

Installer

‒

MltClt.StrComTest

Parameter

Repeat cycle time of relay control for timer

‒

Repetition cycle time for timer 2

User

Device > Multifunction relay > Timer > Repeat cycle for timer

  • daily
  • Once
  • Weekly

‒

‒

User

‒

MltFncSw.Tmr.TmCtlCyc

Parameter

Operating mode of multifunction relay

Mlt.OpMode

Operating mode of the multifunction relay 1 and 2

User

Device > Multifunction relay > Operating mode

  • Off: The multifunction relay is always in non-operative mode.
  • On: The multifunction relay is permanently activated.
  • Automatic generator request: The Sunny Island automatically requests the generator. In the event of a generator request, the multifunction relay is activated.
  • 1-stage load shedding: When the generator is connected, the Sunny Island stops the load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • 1-stage load shedding or 1st stage with 2-stage load shedding: When the upper SOC threshold is reached, the Sunny Island ends load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • 1st stage with 2-stage load shedding: When the upper SOC threshold is reached, the Sunny Island ends load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • Timer 1: the Sunny Island controls external processes dependent on time. When the set time for this timer is reached, the multifunction relay is activated.
  • Timer 2: The Sunny Island controls external processes dependent on time. When the set time for this timer is reached, the multifunction relay is activated.
  • Control of add. loads: The Sunny Island controls external processes time-dependently. When the set time for this timer is reached, the multifunction relay is activated.
  • Relay on if generator running: Relay is activated when generator is running: When the generator is in operation, the multifunction relay is activated.
  • Relay on if ext. source available: When the voltage and frequency of the external energy source are within the valid range for the connection, the multifunction relay is activated.
  • Relay on if grid is available: When the utility grid is connected, the multifunction relay is activated.
  • Relay off in case of fault: When an error message is pending, the multifunction relay is deactivated.
  • Relay on in case of warning: When a warning is pending, the multifunction relay is activated.
  • Relay on if cluster running: When the Sunny Island or the cluster is in operation, the multifunction relay is activated.
  • Battery compartment fan: The Sunny Island controls the battery room fan. When the battery room is to be ventilated, the multifunction relay is activated.
  • Electrolyte pump: The Sunny Island controls the electrolyte pump of the battery. When the electrolyte is to be circulated, the multifunction relay is activated.
  • ComSync: .
  • Relay on with power limitation: When the Sunny Island limits its power, the multifunction relay is deactivated.
  • Network disconnect in emer op: Triggering of contactors for grid disconnection in the battery backup system
  • Earthing in emer op
  • Battery fan in Multicluster: The Sunny Island controls the battery room fan for all clusters together. When the battery room is to be ventilated, the multifunction relay is activated.
  • Load shedding in Multicluster: When all batteries have reached the upper SOC threshold, the Sunny Island ends load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • Redundant grid disconnection control: Triggering of the grounding in the battery backup system (Triggering of earthing in backup operation)

‒

‒

User

‒

MltFncSw.OpMode

Parameter

Slave 1: Operating mode of multifunction relay

‒

Operating mode of the multifunction relay 1 and 2 in Slave 1

User

Device > Multifunction relay > Operating mode slave 1

  • Off: The multifunction relay is always in non-operative mode.
  • On: The multifunction relay is permanently activated.
  • Automatic generator request: The Sunny Island automatically requests the generator. In the event of a generator request, the multifunction relay is activated.
  • 1-stage load shedding: When the generator is connected, the Sunny Island stops the load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • 1-stage load shedding or 1st stage with 2-stage load shedding: When the upper SOC threshold is reached, the Sunny Island ends load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • 1st stage with 2-stage load shedding: When the upper SOC threshold is reached, the Sunny Island ends load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • Timer 1: the Sunny Island controls external processes dependent on time. When the set time for this timer is reached, the multifunction relay is activated.
  • Timer 2: The Sunny Island controls external processes dependent on time. When the set time for this timer is reached, the multifunction relay is activated.
  • Control of add. loads: The Sunny Island controls external processes time-dependently. When the set time for this timer is reached, the multifunction relay is activated.
  • Relay on if generator running: Relay is activated when generator is running: When the generator is in operation, the multifunction relay is activated.
  • Relay on if ext. source available: When the voltage and frequency of the external energy source are within the valid range for the connection, the multifunction relay is activated.
  • Relay on if grid is available: When the utility grid is connected, the multifunction relay is activated.
  • Relay off in case of fault: When an error message is pending, the multifunction relay is deactivated.
  • Relay on in case of warning: When a warning is pending, the multifunction relay is activated.
  • Relay on if cluster running: When the Sunny Island or the cluster is in operation, the multifunction relay is activated.
  • Battery compartment fan: The Sunny Island controls the battery room fan. When the battery room is to be ventilated, the multifunction relay is activated.
  • Electrolyte pump: The Sunny Island controls the electrolyte pump of the battery. When the electrolyte is to be circulated, the multifunction relay is activated.
  • ComSync: .
  • Relay on with power limitation: When the Sunny Island limits its power, the multifunction relay is deactivated.
  • Network disconnect in emer op: Triggering of contactors for grid disconnection in the battery backup system
  • Earthing in emer op
  • Battery fan in Multicluster: The Sunny Island controls the battery room fan for all clusters together. When the battery room is to be ventilated, the multifunction relay is activated.
  • Load shedding in Multicluster: When all batteries have reached the upper SOC threshold, the Sunny Island ends load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • Redundant grid disconnection control: Triggering of the grounding in the battery backup system (Triggering of earthing in backup operation)

‒

‒

User

‒

MltFncSw.OpModeSlv1

Parameter

Slave 2: Operating mode of multifunction relay

‒

Operating mode of the multifunction relay 1 and 2 in Slave 2

User

Device > Multifunction relay > Operating mode slave 2

  • Off: The multifunction relay is always in non-operative mode.
  • On: The multifunction relay is permanently activated.
  • Automatic generator request: The Sunny Island automatically requests the generator. In the event of a generator request, the multifunction relay is activated.
  • 1-stage load shedding: When the generator is connected, the Sunny Island stops the load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • 1-stage load shedding or 1st stage with 2-stage load shedding: When the upper SOC threshold is reached, the Sunny Island ends load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • 1st stage with 2-stage load shedding: When the upper SOC threshold is reached, the Sunny Island ends load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • Timer 1: the Sunny Island controls external processes dependent on time. When the set time for this timer is reached, the multifunction relay is activated.
  • Timer 2: The Sunny Island controls external processes dependent on time. When the set time for this timer is reached, the multifunction relay is activated.
  • Control of add. loads: The Sunny Island controls external processes time-dependently. When the set time for this timer is reached, the multifunction relay is activated.
  • Relay on if generator running: Relay is activated when generator is running: When the generator is in operation, the multifunction relay is activated.
  • Relay on if ext. source available: When the voltage and frequency of the external energy source are within the valid range for the connection, the multifunction relay is activated.
  • Relay on if grid is available: When the utility grid is connected, the multifunction relay is activated.
  • Relay off in case of fault: When an error message is pending, the multifunction relay is deactivated.
  • Relay on in case of warning: When a warning is pending, the multifunction relay is activated.
  • Relay on if cluster running: When the Sunny Island or the cluster is in operation, the multifunction relay is activated.
  • Battery compartment fan: The Sunny Island controls the battery room fan. When the battery room is to be ventilated, the multifunction relay is activated.
  • Electrolyte pump: The Sunny Island controls the electrolyte pump of the battery. When the electrolyte is to be circulated, the multifunction relay is activated.
  • ComSync: Multifunction relay is controlled via ComSync.
  • Relay on with power limitation: When the Sunny Island limits its power, the multifunction relay is deactivated.
  • Network disconnect in emer op: Triggering of contactors for grid disconnection in the battery backup system
  • Earthing in emer op
  • Battery fan in Multicluster: The Sunny Island controls the battery room fan for all clusters together. When the battery room is to be ventilated, the multifunction relay is activated.
  • Load shedding in Multicluster: When all batteries have reached the upper SOC threshold, the Sunny Island ends load shedding. When the loads are to be shed, the multifunction relay is deactivated.
  • Redundant grid disconnection control: Triggering of the grounding in the battery backup system (Triggering of earthing in backup operation)

‒

‒

User

‒

MltFncSw.OpModeSlv2

Measured value

Slave 1: Multifunction relay status

‒

Multifunction relay status 1 and 2 of Slave 1

Installer

Device > Multifunction relay > Status slave 1

  • Off: Multifunction relay is deactivated.
  • On: Multifunction relay is activated.
  • Information not available

‒

‒

‒

‒

MltFncSw.SttSlv1

Measured value

Slave 2: Multifunction relay status

‒

Multifunction relay status 1 and 2 in Slave 2

Installer

Device > Multifunction relay > Status slave 2

  • Off: Multifunction relay is deactivated.
  • On: Multifunction relay is activated.
  • Information not available

‒

‒

‒

‒

MltFncSw.SttSlv2

Parameter

Device class

MainModel

‒

User

Type Label > Type Label > Device class

  • Battery Inverter

Battery Inverter

‒

‒

‒

Nameplate.MainModel

Parameter

Device type

Model,DeviceType

‒

User

Type Label > Type Label > Device type

  • Sunny Island 4.4M
  • Sunny Island 6.0H
  • Sunny Island 8.0H

‒

‒

‒

‒

deviceModel

Parameter

Limitation type of generator current

‒

The generator control limits the consumption of generator current.

Installer

Generator > Operation > Type of current limitation

  • Fixed limit value for current limitation
  • Frequency-dependent current limitation

‒

‒

Installer

‒

Operation.ALimMod

Parameter

Automatic frequency control

‒

–

Installer

AC Side > Operation > Automatic frequency control

  • Off: Disable
  • On: Enable

‒

‒

Installer

‒

Operation.AutoHzCtl

Parameter

Cluster behaviour when a device fails

‒

–

Installer

Device > Operation > Cluster behaviour when a device fails

  • Further operation
  • Stop all devices

‒

‒

Installer

‒

Operation.CltFltMod

Measured value

Power supply status

‒

‒

User

AC Side > Operation > Power supply status

  • Off
  • Mains connected
  • Backup not available
  • Backup
  • Information not available

‒

‒

‒

‒

Operation.CsmpGriConnStt

Parameter

Energy saving mode

‒

‒

Installer

System and device control > Operation > Energy saving mode

  • Off
  • On

‒

‒

InstallerDevice Control ObjectOperation.EnSavMod

Measured value

Recommended action

Op.Prio

‒

User

Status > Operation > Current event > Recommended action

  • Contact manufacturer
  • Contact installer
  • invalid
  • none

‒

‒

‒

‒

Operation.Evt.Prio

Measured value

Message

‒

‒

User

Status > Operation > Current event > Message

  • none

‒

‒

‒

‒

Operation.Evt.Msg

Measured value

Fault correction measure

‒

‒

User

Status > Operation > Current event > Fault correction measure

  • none

‒

‒

‒

‒

Operation.Evt.Dsc

Measured value

Reason for generator request

‒

–

User

Generator > Operation > Reason for requesting generator

  • Battery: State-of-charge-dependent request
  • No request: –
  • Load: Load-dependent request
  • Time control: Time-controlled request
  • Manual one hour: Manually requested for one hour.
  • Manual start
  • External source: External generator request
  • Information not available

‒

‒

‒

‒

Operation.GnDmdReas

Parameter

Sensitivity of generator failure detection

‒

Anti-islanding Sensitivity of the generator fault recognition (anti-islanding)

Installer

Generator > Operation > Sensitivity of generator failure detection

  • Low
  • Medium
  • Normal
  • High

‒

‒

Installer

‒

Operation.GnFltDet

Parameter

Grid creating generator

‒

External energy sources in Off-Grid mode

User

AC Side > Operation > Grid creating generator

  • No: Only AC sources in the stand-alone grid, no generator in the off-grid system
  • Generator: –
  • Mains: Utility grid
  • Mains and generator: Generator and utility grid

‒

‒

Installer

‒

Operation.GriCreaSrc

Measured value

Condition

Op.Health

‒

User

Status > Operation > Condition

  • Fault
  • Off
  • Ok
  • Warning

‒

‒

‒

‒

Operation.Health

Measured value

Operating status Master (Phase L1)

‒

Operating state of the Sunny Island

User

Status > Operation > Condition > Master

  • Fault
  • Off
  • Ok
  • Warning

‒

‒

‒

‒

Operation.Health.Master

Measured value

Operating status Slave1 (Phase L2)

‒

–

Installer

Status > Operation > Condition > Slave 1

  • Fault
  • Off
  • Ok
  • Warning

‒

‒

‒

‒

Operation.Health.Slv1

Measured value

Operating status Slave2 (Phase L3)

‒

–

Installer

Status > Operation > Condition > Slave 2

  • Fault
  • Off
  • Ok
  • Warning

‒

‒

‒

‒

Operation.Health.Slv2

Parameter

Load parameter

Op.StoFncSet

‒

Installer

Device > Operation > Load parameter

  • Load preset

‒

‒

Installer

‒

Operation.LodFnc

Parameter

Operating condition

Op.OpModSet

‒

User

Device > Operation > Operating condition

  • Stop
  • Start

‒

‒

Installer

‒

Operation.OpMod

Measured value

Plant mains connection

‒

‒

User

AC Side > Operation > Mains connection

  • Separated
  • Public electricity mains
  • Island mains
  • Information not available

‒

‒

‒

‒

Operation.PvGriConn

Parameter

Time-controlled inverter operation

‒

–

User

Device > Operation > Time control > Activated

  • Yes: Enable
  • No: Disable

‒

‒

User

‒

Operation.TmCtl.IsOn

Parameter

Repeat cycle for time-controlled inverter op.

‒

–

User

Device > Operation > Time control > Repeat cycle

  • daily
  • Once
  • Weekly: Weekly

‒

‒

User

‒

Operation.TmCtl.RptCyc

Parameter

Reset operating data

Op.FncSetIstl

‒

Installer

Device > Operation > Reset operating data

  • Battery
  • Inverter
  • Reset events
  • Reset energy logger
  • Reset operation inhibition
  • Operating time
  • Execute all
  • Reset network parameter
  • AC grid
  • Generator
  • All Sunny Island chargers

‒

‒

Installer

‒

Operation.ValRsIstl

Measured value

Status of active power limitation

‒

‒

User

System and device control > Operation > Active power limitation P > Status

  • Off
  • On
  • Active
  • Limits possible active power
  • Information not available

‒

‒

‒

‒

Operation.WCtl.Stt

Parameter

Operating mode for load unbalance limitation

‒

Type of PV system feed-in

User

System and device control > Grid connection point

  • Off
  • On

‒

‒

User

‒

PCC.WMaxAsymMod

Parameter

Operating mode of act. power limit. at grid connection pt

‒

‒

User

System and device control > Grid connection point > Operating mode of active power limitation

  • Off
  • Fixed specification in Watt
  • Fixed specification in percentages

Off

‒

Installer

‒

PCC.WMaxMod

Parameter

Power feedback to public grid allowed

‒

Type of reverse feeding into the utility grid

Installer

AC Side > Public electricity mains > Feed-back permitted

  • Yes: If the grid operation mode in the installation assistant has been selected, the value Yes is fixed.
  • No: Yes: If the stand-alone mode in the installation assistant has been selected, the values Yes and No are selectable.

‒

‒

Installer

‒

PubGri.FeedPerm

Parameter

Network request via battery state of charge switched on

‒

Enable grid request based on battery state of charge

Installer

AC Side > Public electricity mains > Network request via battery state of charge > Activated

  • Yes: Enable
  • No: Disable

‒

‒

Installer

‒

PubGri.GriDmdBatCha.IsOn

Parameter

Network request via power switched on

‒

–

User

AC Side > Public electricity mains > Network request via power > Activated

  • Yes: Enable
  • No: Disable

‒

‒

Installer

‒

PubGri.GriDmdW.IsOn

Parameter

Manual control of network connection

‒

Visible if the parameter "Grid request based on battery state of charge switched on" or "Grid request based on power switched on" is activated

User

AC Side > Public electricity mains > Manual control

  • Stop: Stop
  • Automatic: automatically
  • Start: Start

‒

‒

User

‒

PubGri.ManCtl

Parameter

Network request via charge type

‒

–

User

AC Side > Public electricity mains > Network request via charge type > Charge type

  • Off
  • Full and equalization charge
  • Full charge
  • Equalization charge

‒

‒

Installer

‒

PubGri.GriDmdChaMod.ChaMod

Measured value

Status of utility grid

‒

(Utility grid)

User

AC Side > Public electricity mains > Status

  • Fault: An error occurred when connecting.
  • Off: Grid operation is disabled.
  • Waiting for valid AC grid: Grid monitoring started.
  • Wait: Waiting until the stand-alone grid is synchronized with the utility grid.
  • Initialization: Utility grid has been detected.
  • Mains oper. without feed back: The stand-alone grid is synchronized with and connected to the utility grid.
  • Energy saving in the network: Sunny Island is in energy-saving mode.
  • End energy saving in the network: Sunny Island is ending the energy-saving mode.
  • Start energy saving in the network: The Sunny Island is switching to energy-saving mode.
  • Mains operation with feedback: Grid feed-in into the utility grid is possible.
  • Information not available

‒

‒

‒

‒

PubGri.Stt

Parameter

Rise in self-consumption switched on

‒

–

User

Device > Self-consumption > Rise in self-consumption switched on

  • Yes: Enable
  • No: Disable

‒

‒

Installer

‒

SelfCsmp.SelfCsmpIncIsOn

Parameter

Energy saving mode switched on

‒

–

Installer

AC Side > Energy saving mode > Activated

  • Yes: Enable
  • No: Disable

‒

‒

Installer

‒

SltMod.IsOn

Measured value

Speedwire connection status of SMACOM A

‒

‒

User

System communication > Speedwire > SMACOM A > Status

  • Fault
  • Ok
  • Warning
  • No connection

‒

‒

‒

‒

Spdwr.ComSocA.Stt

Measured value

Connection speed of SMACOM A

‒

‒

User

System communication > Speedwire > SMACOM A > Connection speed

  • 10 Mbit/s
  • 100 Mbit/s
  • No connection speed set

‒

‒

‒

‒

Spdwr.ComSocA.ConnSpd

Measured value

Duplex mode of SMACOM A

‒

‒

Installer

System communication > Speedwire > SMACOM A > Duplex mode

  • Half duplex
  • Full duplex
  • No duplex mode set

‒

‒

‒

‒

Spdwr.ComSocA.DpxMode

Parameter

Automatic speedwire configureation switched on

‒

‒

User

System communication > Speedwire > Automatic configuration switched on

  • Yes: Enable
  • No: Disable

Yes: Aktivieren

‒

User

‒

Spdwr.AutoCfgIsOn

Parameter

Type of AC subdistribution

‒

Type of Multicluster Box

User

AC Side > System > Type of AC distribution

  • -------
  • Multicluster Box 6
  • Multicluster Box 12
  • Multicluster Box 36
  • Multicluster Box 12-2

‒

‒

Installer

‒

Sys.AcTyp

Parameter

Type of additional DC sources

‒

–

Installer

DC Side > System > Type of additional DC sources

  • AC sources and DC charge controllers
  • Other DC charge controllers
  • Communicatively coupled DC charge controller

‒

‒

Installer

‒

Sys.AuxDcTyp

Parameter

Initiate device restart

DeviceReset,DevRs

–

Installer

Device > System > Initiate device restart

  • Execute

‒

‒

Installer

‒

Sys.DevRstr

Measured value

Status of the firmware update

‒

‒

User

Status > Update > Status

  • Update is currently being received
  • Update is currently running
  • Update performed successful
  • An error occurred during the update
  • No update status set

‒

‒

‒

‒

Upd.Stt

Measured value

Status of the Webconnect functionality

‒

‒

User

External Communication > Webconnect > Status

  • Off
  • Ok
  • Faulty communication
  • No connection
  • Default gateway not configured
  • DNS server not configured
  • No reply to DNS request
  • SIP proxy DNS resolution failed
  • Stun server DNS resolution failed
  • No reply to request to Stun server
  • No reply to SIP option packs
  • Registration rejected by SIP registrar
  • Unknown SIP registry
  • Connection establishment
  • Registration of the SIP registry has not responded

‒

‒

‒

‒

WebConn.Stt

Parameter

Webconnect functionality switched on

WebConn.IsOn

‒

User

External Communication > Webconnect > Activated

  • Yes: Restart
  • No: Do not restart

Yes: Neu starten

‒

User

‒

WebConn.IsOn

Measured value

Status of WLAN scan

‒

‒

User

System communication > WLAN > Status of the scan

  • No scan completed
  • Scan is active
  • Scan failed
  • Scan successful

‒

‒

‒

‒

Wl.AcqStt

Parameter

Automatic configuration of WLAN is turned on

‒

‒

User

System communication > WLAN > Automatic configuration switched on

  • Yes: Restart
  • No: Do not restart

Yes: Neu starten

‒

User

‒

Wl.AutoCfgIsOn

Measured value

WLAN connection status

‒

‒

User

System communication > WLAN > Connection status

  • Off
  • Ok
  • No connection
  • Connection establishment
  • Error while connecting
  • WPS is active

‒

‒

‒

‒

Wl.ConnStt

Parameter

Perform WLAN scan

‒

‒

User

System communication > WLAN > Perform scan

  • Execute

‒

‒

User

‒

Wl.DoAcq

Parameter

Activate WPS

‒

‒

User

System communication > WLAN > Activate WPS

  • Execute

‒

‒

User

‒

Wl.DoWPS

Parameter

WLAN is turned on

‒

‒

User

System communication > WLAN > Activated

  • Yes: Restart
  • No: Do not restart

Yes: Neu starten

‒

User

‒

Wl.IsOn

Parameter

Encryption for WLAN

‒

‒

User

System communication > WLAN > Security > Encryption

  • WPA-AES
  • WPA2-AES

WPA2-AES

‒

User

‒

Wl.Sec.Cry

Parameter

Soft-access-point is turned on

‒

‒

User

System communication > WLAN > Soft-access-point is turned on

  • Yes: Restart
  • No: Do not restart

Yes: Neu starten

‒

User

‒

Wl.SoftAcsIsOn

Measured value

Battery current

‒

Total battery current of the cluster

User

Battery > Battery > Current

A

‒

0.001

‒

‒

Bat.Amp

Measured value

Fault battery state of charge

‒

Estimated error of the battery state of charge (SOC)

Installer

Battery > Battery > Fault state of charge

%

‒

0.1

‒

‒

Bat.BatChaDif

Parameter

Rated battery capacity

‒

Battery nominal capacity C10

User

Battery > Battery > Nominal capacity

0 Ah to 10000 Ah

‒

1

Installer

‒

Bat.CapacRtg

Parameter

Battery nominal capacity

‒

‒

User

Battery > Battery > Rated capacity

0 Wh to 2147484 Wh

‒

1

‒

‒

Bat.CapacRtgWh

Measured value

Current battery state of charge

‒

State of charge of the battery (SOC) based on the nominal battery capacity

User

Battery > Battery > State of charge

%

‒

1

‒

‒

Bat.ChaStt

Parameter

Output resistance of battery connection

‒

–

Installer

Battery > Battery > Output resistance DC connection

0.000 Ω to 0.100 Ω

‒

0.001

Installer

‒

Bat.DcRis

Measured value

Current battery capacity

‒

Ratio of currently usable capacity to the rated value of the battery

User

Battery > Battery > Diagnosis > Current capacity

%

‒

1

‒

‒

Bat.Diag.ActlCapacNom

Measured value

Number of battery charge throughputs

‒

A nominal energy throughput is the calculated result of one full charge and discharge of the battery.

User

Battery > Battery > Diagnosis > Rated capacity throughput

‒

‒

1

‒

‒

Bat.Diag.CapacThrpCnt

Measured value

Charge factor: ratio of battery charge/discharge

‒

–

Installer

Battery > Battery > Diagnosis > Charge factor

‒

‒

0.001

‒

‒

Bat.Diag.ChaFact

Measured value

Maximum battery current in charge direction

‒

‒

Installer

Battery > Battery > Diagnosis > Max. occurred charge current

A

‒

0.001

‒

‒

Bat.Diag.ChaAMax

Measured value

Maximum battery current in discharge direction

‒

‒

Installer

Battery > Battery > Diagnosis > Max. occurred discharge current

A

‒

0.001

‒

‒

Bat.Diag.DschAMax

Measured value

Frequency distribution of the state of charge, |s0| % > SOC >= |s1|%

‒

–

Installer

Battery > Battery > Diagnosis > Frequency distribution of the state of charge

%

‒

1

‒

‒

Bat.Diag.SocFrqDstr

Measured value

Operating time of battery statistics counter

‒

–

Installer

Battery > Battery > Diagnosis > Operating time statistics counter

s

‒

1

‒

‒

Bat.Diag.StatTm

Measured value

Lowest measured battery temperature

‒

‒

Installer

Battery > Battery > Diagnosis > Lowest measured temperature

°C

‒

0.1

‒

‒

Bat.Diag.TmpValMin

Measured value

Highest measured battery temperature

‒

‒

Installer

Battery > Battery > Diagnosis > Highest measured temperature

°C

‒

0.1

‒

‒

Bat.Diag.TmpValMax

Measured value

Amp hours counter for battery charge

‒

–

User

Battery > Battery > Diagnosis > Energy absorbed charge amount

Ah

‒

1

‒

‒

Bat.Diag.TotAhIn

Measured value

Amp hours counter for battery discharge

‒

–

User

Battery > Battery > Diagnosis > Charge amount released

Ah

‒

1

‒

‒

Bat.Diag.TotAhOut

Measured value

Max. occurred battery voltage

‒

Maximal aufgetretene Batteriespannung des aktuellen Tages

Installer

Battery > Battery > Diagnosis > Maximum voltage

V

‒

0.01

‒

‒

Bat.Diag.VolMax

Measured value

Remaining time until full charge

‒

–

User

Battery > Battery > Remaining time until full charge

s

‒

1

‒

‒

Bat.FulChaRmgTm

Measured value

Remaining time until equalization charge

‒

–

User

Battery > Battery > Remaining time until equalization charge

s

‒

1

‒

‒

Bat.EqChaRmgTm

Parameter

Battery switch-on limit after overtemp. shutdown

‒

Battery temperature as connection limit after overtemperature disconnection

Installer

Battery > Battery > Switch-on limit after overtemperature shutdown

°C

‒

0.1

Installer

‒

Bat.OvTmpRstr

Measured value

Remaining absorption time

‒

Remaining absorption time until completion of the current battery charge phase (see parameter Active battery charging mode)

Installer

Battery > Battery > Remaining absorption time

s

‒

1

‒

‒

Bat.RmgChaTm

Parameter

Max. battery temperature

‒

–

Installer

Battery > Battery > Maximum temperature

°C

‒

1

Installer

‒

Bat.TmpMax

Measured value

Battery temperature

‒

–

User

Battery > Battery > Temperature

°C

‒

0.1

‒

‒

Bat.TmpVal

Measured value

Battery voltage

‒

–

User

Battery > Battery > Voltage

V

‒

0.01

‒

‒

Bat.Vol

Parameter

Rated battery voltage

‒

–

User

Battery > Battery > Nominal voltage

40 V to 48 V

‒

1

‒

‒

Bat.VRtg

Measured value

Battery charge

‒

Energy meter for battery charging in kWh

User

Battery > Battery charge > Battery charge

Wh

‒

1

‒

‒

BatChrg.BatChrg

Parameter

Process specification battery charge current

‒

‒

Installer

Battery > Battery charge > Process specification battery charge current

−400.0 A to +400.0 A

‒

0.1

‒

‒

BatChrg.BatChrgSetA

Measured value

Present battery charge

‒

‒

User

Battery > Battery charge > Present battery charge

W

‒

1

‒

‒

BatChrg.CurBatCha

Measured value

Battery discharge

‒

Energy meter for battery discharging in kWh

User

Battery > Battery discharge > Battery discharge

Wh

‒

1

‒

‒

BatDsch.BatDsch

Parameter

Process specification battery discharge current

‒

‒

Installer

Battery > Battery discharge > Process specification battery discharge current

−400.0 A to +400.0 A

‒

0.1

‒

‒

BatDsch.BatDschSetA

Measured value

Present battery discharge

‒

‒

User

Battery > Battery discharge > Present battery discharge

W

‒

1

‒

‒

BatDsch.CurBatDsch

Parameter

Batt. manuf's max. charge capac.

‒

Nominal power of the cluster

Installer

Battery > Battery switch > Max. charge capacity

0 W to 100000 W

‒

1

‒

‒

BatConv.WMaxCha

Parameter

Batt. manuf's max. disch. capac.

‒

‒

Installer

Battery > Battery switch > Max. discharge capacity

0 W to 100000 W

‒

1

‒

‒

BatConv.WMaxDsch

Parameter

Upper state of charge for reactivating feed-in

‒

‒

Installer

System and device control > Areas of application > Upper state of charge for reactivating feed-in

0 % to 90 %

‒

1

Installer

‒

BatUsDm.ChaSttFeedAct

Parameter

Lower state of charge for locking feed-in

‒

‒

Installer

System and device control > Areas of application > Lower state of charge for locking feed-in

%

‒

1

Installer

‒

BatUsDm.ChaSttFeedIna

Parameter

Lower lmt deep disch. protect area prior shutdown

‒

Lower limit of the deep-discharge protection range for disconnection (%) of the battery capacity

Installer

Battery > Areas of application > Lower lmt deep disch. protect area prior shutdown

%

‒

1

Installer

‒

BatUsDm.DschProDmLim

Parameter

Minimum width of deep discharge protection area

‒

Minimum width of the deep-discharge protection range (%) of the battery capacity (BatResSOC)

Installer

Battery > Areas of application > Minimum width of deep discharge protection area

2 % to 50 %

‒

1

Installer

‒

BatUsDm.DschProDmMin

Parameter

Minimum width of backup power area

‒

Minimum width of the backup power supply range on the longest day of the year as a percentage of the battery capacity (BUResSOC)

Installer

Battery > Areas of application > Minimum width of backup power area

0 % to 100 %

‒

1

Installer

‒

BatUsDm.BckDmMin

Parameter

Area width for conserving battery state of charge

‒

Width of the range for the maintenance of the battery state of charge (%) of the nominal capacity (PVResSOC)

Installer

Battery > Areas of application > Area width for conserving battery state of charge

4 % to 20 %

‒

1

Installer

‒

BatUsDm.SelfCsmpBrd

Parameter

Minimum width of own consumption area

‒

Minimum width of the self-consumption range on the shortest day of the year as a percentage of the battery capacity (MinSlfCsmpSOC): The setting of this parameter to 70% for lithium-ion batteries corresponds to a discharge of 30% until the SOC is reached. The setting of this parameter to 35% for lead-acid batteries corresponds to a discharge of 65% until the SOC is reached.

Installer

Battery > Areas of application > Minimum width of own consumption area

0 % to 100 %

‒

1

Installer

‒

BatUsDm.SelfCsmpBrdMin

Measured value

Lower discharge limit for private consumption range

‒

With this updated display value, the Sunny Island inverter informs of the state of charge up to which the battery for increased self-consumption is discharged.

Installer

Battery > Areas of application > Lower discharge limit for private consumption range

%

‒

1

‒

‒

BatUsDm.SelfCsmpDmLim

Measured value

Current battery charging set voltage

‒

–

User

Battery > Charge > Current set charging voltage

V

‒

0.01

‒

‒

Cha.ActlChaVolSpt

Parameter

Voltage setpoint with deactivated battery mgmt

‒

Manual setpoint of the battery charging voltage with disabled battery management

Installer

Battery > Charge > Voltage setpoint with deactivated BMS

41.00 V to 63.00 V

‒

0.01

Installer

‒

Cha.BMSInaVol

Parameter

Battery boost charge time

‒

Absorption time for boost charge

Installer

Battery > Charge > Time for boost charge

1 min to 600 min

‒

1

Installer

‒

Cha.BstChaTmm

Parameter

Cell charge nominal voltage for boost charge

‒

Cell voltage setpoint for boost charge

Installer

Battery > Charge > Cell charge nominal voltage for boost charge

2.20 V to 2.70 V

‒

0.01

Installer

‒

Cha.BstChaVolSpt

Parameter

Maximum battery discharge current

‒

‒

Installer

Battery > Charge > Maximum discharge current

0.000 A to 900.000 A

‒

0.001

Installer

‒

Cha.DschAmpMax

Parameter

Battery discharge cut-off voltage

‒

‒

Installer

Battery > Charge > Discharge cut-off voltage

35.00 V to 63.00 V

‒

0.01

Installer

‒

Cha.DschStopVol

Measured value

Number of battery equalization charges

‒

–

Installer

Battery > Charge > No. of equalization charges

‒

‒

1

‒

‒

Cha.EqChaCnt

Parameter

Cycle time equalization charge

‒

Equalization charge cycle time

Installer

Battery > Charge > Cycle time equalization charge

604800 s to 31536000 s

‒

1

Installer

‒

Cha.EqChaCycTm

Parameter

Cell charge nominal voltage for equalization charge

‒

Cell voltage setpoint for equalization charge

Installer

Battery > Charge > Cell charge nominal voltage for equalization charge

2.30 V to 2.70 V

‒

0.01

Installer

‒

Cha.EqChaVolSpt

Measured value

Relative battery discharge since last equalization charge

‒

‒

Installer

Battery > Charge > Relative battery discharge since last equalization charge

%

‒

1

‒

‒

Cha.EqDschNom

Parameter

Battery equalization charge time

‒

Absorption time for equalization charge

Installer

Battery > Charge > Time for equalization charge

1 h to 48 h

‒

1

Installer

‒

Cha.EqChaTmh

Measured value

Number of battery full charges

‒

–

Installer

Battery > Charge > No. of full charges

‒

‒

1

‒

‒

Cha.FulChaCnt

Parameter

Cycle time full charge

‒

Cycle time of full charge

Installer

Battery > Charge > Cycle time full charge

86400 s to 15552000 s

‒

1

Installer

‒

Cha.FulChaCycTm

Parameter

Cell charge nominal voltage for full charging

‒

Cell voltage setpoint for full charge

Installer

Battery > Charge > Cell charge nominal voltage for full charging

2.30 V to 2.70 V

‒

0.01

Installer

‒

Cha.FulChaVolSpt

Parameter

Battery full charge time

‒

Absorption time for full charge

Installer

Battery > Charge > Time for full charge

1 h to 20 h

‒

1

Installer

‒

Cha.FulChaTmh

Measured value

Relative battery discharge since last full charge

‒

‒

Installer

Battery > Charge > Relative battery discharge since last full charge

%

‒

1

‒

‒

Cha.FulDschNom

Parameter

Max. battery charging current

‒

–

User

Battery > Charge > Maximum charging current

10.000 A to 900.000 A

‒

0.001

Installer

‒

Cha.MaxChaAmp

Parameter

Battery temperature compensation

‒

Automatic temperature compensation from 20°C

Installer

Battery > Charge > Temperature compensation

0 V/°C to 0 V/°C

‒

0.001000

Installer

‒

Cha.TmpCpn

Parameter

Cell charge nominal voltage for float charge

‒

Cell voltage setpoint for float charge

Installer

Battery > Charge > Cell charge nominal voltage for float charge

2.20 V to 2.40 V

‒

0.01

Installer

‒

Cha.TrcChaVolSpt

Parameter

Max. battery charge capac.

‒

‒

Installer

Battery > Battery management system > Max. battery charge capac.

W

‒

1

InstallerDevice Control ObjectCmpBMS.BatChaMaxW

Parameter

Max. battery discharge capac.

‒

‒

Installer

Battery > Battery management system > Max. battery discharge capac.

W

‒

1

InstallerDevice Control ObjectCmpBMS.BatDschMaxW

Parameter

Mains exch. capac. target value

‒

‒

Installer

Battery > Battery management system > Mains exch. capac. target value

W

‒

1

InstallerDevice Control ObjectCmpBMS.GridWSpt

Measured value

Inverter temperature

Inv.TmpVal

Temperature of the heat sink in the Sunny Island: The temperature of the heat sink is displayed in the master of a cluster.

Installer

Device > Cooling system > Inverter > Temperature

°C

‒

0.1

‒

‒

Coolsys.Inverter.TmpVal

Measured value

Transformer temperature

‒

Temperature of the transformer: The temperature of the transformer is displayed in the master of a cluster.

Installer

Device > Cooling system > Transformer > Temperature

°C

‒

0.1

‒

‒

Coolsys.Tr.TmpVal

Parameter

Time of the update

‒

Point in time for performing the automatic firmware update

User

System communication > Device update > Time of the automatic update

0 to 86399

‒

1

User

‒

DevUpd.AutoUpdTm

Parameter

Start feed-in PV

‒

Start time for PV grid feed-in

Installer

AC Side > External network > Start feed-in

0 to 86399

‒

1

Installer

‒

ExtGri.StrPvFeedTm

Parameter

Stop feed-in PV

‒

Stop time for PV grid feed-in

Installer

AC Side > External network > Stop feed-in

0 to 86399

‒

1

Installer

‒

ExtGri.StopPvFeedTm

Measured value

Electricity external power connection phase A

‒

Current of the external grid connection at line conductor L1

User

AC Side > Measurements of external power connection > Phase currents > Phase L1

A

‒

0.001

‒

‒

ExtGridMs.A.phsA

Measured value

Electricity external power connection phase B

‒

Current of the external grid connection at Slave 1 / line conductor L2

User

AC Side > Measurements of external power connection > Phase currents > Phase L2

A

‒

0.001

‒

‒

ExtGridMs.A.phsB

Measured value

Electricity external power connection phase C

‒

Current of the external grid connection at Slave 2 / line conductor L3

User

AC Side > Measurements of external power connection > Phase currents > Phase L3

A

‒

0.001

‒

‒

ExtGridMs.A.phsC

Measured value

Grid frequency of external power connection

‒

Frequency of external energy source

User

AC Side > Measurements of external power connection > Grid frequency

Hz

‒

0.01

‒

‒

ExtGridMs.Hz

Measured value

Lowest measured frequency

‒

‒

Installer

AC Side > Measurements of external power connection > Lowest measured frequency

Hz

‒

0.01

‒

‒

ExtGridMs.HzMin

Measured value

Highest measured frequency

‒

‒

Installer

AC Side > Measurements of external power connection > Highest measured frequency

Hz

‒

0.01

‒

‒

ExtGridMs.HzMax

Measured value

Voltage external power connection phase A

‒

Voltage of the external grid connection at line conductor L1

User

AC Side > Measurements of external power connection > Phase voltage > Phase L1

V

‒

0.01

‒

‒

ExtGridMs.PhV.phsA

Measured value

Voltage external power connection phase B

‒

Voltage of the external grid connection at Slave 1 / line conductor L2

User

AC Side > Measurements of external power connection > Phase voltage > Phase L2

V

‒

0.01

‒

‒

ExtGridMs.PhV.phsB

Measured value

Voltage external power connection phase C

‒

Voltage of the external grid connection at Slave 2 / line conductor L3

User

AC Side > Measurements of external power connection > Phase voltage > Phase L3

V

‒

0.01

‒

‒

ExtGridMs.PhV.phsC

Parameter

Cut-off time until connection to external network

‒

Lock time until connection to the external grid after reverse power or relay protection

Installer

AC Side > Measurements of external power connection > Cut-off time until shutdown

0 s to 3600 s

‒

1

Installer

‒

ExtGridMs.ProLokTm

Measured value

Total current external network connection

‒

Total current of the external grid connection

User

AC Side > Measurements of external power connection > Phase total Current

A

‒

0.001

‒

‒

ExtGridMs.TotA

Measured value

Reactive power external power connection

‒

Total reactive power of the external grid connection

User

AC Side > Measurements of external power connection > Reactive power

VAr

‒

1

‒

‒

ExtGridMs.TotVAr

Measured value

Output external power connection

‒

Total active power of the external grid connection

User

AC Side > Measurements of external power connection > Power

W

‒

1

‒

‒

ExtGridMs.TotW

Measured value

Reactive power external power connection phase A

‒

Reactive power of the external grid connection at line conductor L1

User

AC Side > Measurements of external power connection > Reactive power > Phase L1

VAr

‒

1

‒

‒

ExtGridMs.VAr.phsA

Measured value

Reactive power external power connection phase B

‒

Reactive power of the external grid connection at Slave 1 / line conductor L2

User

AC Side > Measurements of external power connection > Reactive power > Phase L2

VAr

‒

1

‒

‒

ExtGridMs.VAr.phsB

Measured value

Reactive power external power connection phase C

‒

Reactive power of the external grid connection at Slave 2 / line conductor L3

User

AC Side > Measurements of external power connection > Reactive power > Phase L3

VAr

‒

1

‒

‒

ExtGridMs.VAr.phsC

Measured value

Output external power connection phase A

‒

Total active power of the external grid connection at line conductor L1

User

AC Side > Measurements of external power connection > Power per phase > Phase L1

W

‒

1

‒

‒

ExtGridMs.W.phsA

Measured value

Output external power connection phase B

‒

Total active power of the external grid connection at Slave 1 / line conductor L2

User

AC Side > Measurements of external power connection > Power per phase > Phase L2

W

‒

1

‒

‒

ExtGridMs.W.phsB

Measured value

Output external power connection phase C

‒

Total active power of the external grid connection at Slave 2 / line conductor L3

User

AC Side > Measurements of external power connection > Power per phase > Phase L3

W

‒

1

‒

‒

ExtGridMs.W.phsC

Parameter

Rated generator current

‒

–

User

Generator > Generator > Nominal current

A

‒

0.001

Installer

‒

Gn.ARtg

Measured value

Number of generator starts

‒

–

User

Generator > Generator > Diagnosis > Number of starts

‒

‒

1

‒

‒

Gn.Diag.StrCnt

Parameter

Voltage monit. gener. lower minimum threshold

‒

Lower minimum threshold of PV array voltage for voltage monitoring

Installer

Generator > Generator > Voltage monitoring > Lower minimum threshold

V

‒

0.01

Installer

‒

Gn.VolCtl.Min

Parameter

Voltage monit. gener. upper maximum threshold

‒

Upper maximum threshold of PV array voltage for voltage monitoring

Installer

Generator > Generator > Voltage monitoring > Upper maximum threshold

V

‒

0.01

Installer

‒

Gn.VolCtl.Max

Parameter

Voltage monit. gener. hysteresis min. threshold

‒

‒

Installer

Generator > Generator > Voltage monitoring > Hysteresis minimum threshold

0.00 V to 10.00 V

‒

0.01

Installer

‒

Gn.VolCtl.ReconMinDif

Parameter

Voltage monit. hysteresis generator max. threshold

‒

‒

Installer

Generator > Generator > Voltage monitoring > Hysteresis maximum threshold

0.00 V to 10.00 V

‒

0.01

Installer

‒

Gn.VolCtl.ReconMaxDif

Parameter

Frequency monit. generator lower minimum threshold

‒

Lower minimum threshold of generator frequency for frequency monitoring

Installer

Generator > Generator > Frequency monitoring > Lower minimum threshold

Hz

‒

0.01

Installer

‒

Gn.FrqCtl.Min

Parameter

Frequency monit. generator without max. threshold

‒

Upper maximum threshold of generator frequency for frequency monitoring

Installer

Generator > Generator > Frequency monitoring > Upper maximum threshold

Hz

‒

0.01

Installer

‒

Gn.FrqCtl.Max

Parameter

Frequency monit. gener. hysteresis min. threshold

‒

‒

Installer

Generator > Generator > Frequency monitoring > Hysteresis minimum threshold

0.00 Hz to 2.00 Hz

‒

0.01

Installer

‒

Gn.FrqCtl.ReconMinDif

Parameter

Freq. Monit. generator hysteresis max. threshold

‒

‒

Installer

Generator > Generator > Frequency monitoring > Hysteresis maximum threshold

0.00 Hz to 2.00 Hz

‒

0.01

Installer

‒

Gn.FrqCtl.ReconMaxDif

Parameter

Voltage monitoring generator maximum reverse power

‒

Maximum reverse power for voltage monitoring of generator

Installer

Generator > Generator > Power monitoring > Maximum reverse power

W

‒

1

Installer

‒

Gn.WMon.RvPwrMax

Parameter

Volt. monit. gener. max. reverse power trip. time

‒

Time for reverse power or reverse current for voltage monitoring of generator

Installer

Generator > Generator > Power monitoring > Maximum reverse power tripping time

0 s to 900 s

‒

1

Installer

‒

Gn.WMon.RvPwrMaxTms

Parameter

Limit battery state of charge generator start in time range

‒

Battery state of charge limit for generator request in standard time period: This is the valid threshold without the additional time period.

User

Generator > Generator queries state of charge > Switch-on limit in time range

%

‒

1

Installer

‒

GnDmdBatCha.OnLim

Parameter

Limit battery state of charge gen. shutdown in time range

‒

Battery state of charge limit for end of generator request in standard time period: This is the valid threshold without the additional time period.

User

Generator > Generator queries state of charge > Switch-off limit in time range

%

‒

1

Installer

‒

GnDmdBatCha.OffLim

Parameter

Start time additional time range generator request

‒

–

User

Generator > Generator queries state of charge > Additional time range > Start time

0 to 86399

‒

1

Installer

‒

GnDmdBatCha.AddTm.StrTm

Parameter

Start time range for generator request

‒

Start time of the standard additional time period for generator request; corresponds to the end time of the additional time period

User

Generator > Generator queries state of charge > Additional time range > End time

0 to 86399

‒

1

Installer

‒

GnDmdBatCha.AddTm.StopTm

Parameter

Limit battery state of charge generator stop in add time range

‒

Battery state of charge limit for generator request in additional time period

User

Generator > Generator queries state of charge > Additional time range > Switch-on limit in time range

%

‒

1

Installer

‒

GnDmdBatCha.AddTm.OnLim

Parameter

Limit battery state of charge generator start in add time range

‒

Battery state of charge limit for end of generator request in the additional time period

User

Generator > Generator queries state of charge > Additional time range > Switch-off limit in time range

%

‒

1

Installer

‒

GnDmdBatCha.AddTm.OffLim

Parameter

Start time for time-controlled generator op.

‒

Date and time for start of time-controlled generator operation

User

Generator > Time-controlled generator operation > Start time

dd,MM,yyyy HH:mm:ss

0,00,0000 00:00:00

1

Installer

‒

GnDmdTm.StrTm

Parameter

Operating time for time-controlled generator op.

‒

–

User

Generator > Time-controlled generator operation > Operating time

0 s to 359940 s

‒

1

Installer

‒

GnDmdTm.RunTm

Parameter

Average time for generator request via power

‒

–

User

Generator > Generator request via power > Average time

1 s to 900 s

‒

1

Installer

‒

GnDmdW.WAvTm

Parameter

Generator shutdown load limit

‒

Load limit: Generator shutdown for end of generator request based on power

User

Generator > Generator request via power > Switch-off power

W

‒

1

Installer

‒

GnDmdW.WOff

Parameter

Generator startup load limit

‒

Load limit: Generator start for generator request based on power

User

Generator > Generator request via power > Switch-on power

W

‒

1

Installer

‒

GnDmdW.WOn

Measured value

Generator operating hours

‒

–

User

Generator > Generator measured values > Operating time

s

‒

1

‒

‒

GnMs.TotOpTms

Measured value

Generator output energy

‒

–

User

Generator > Generator measured values > Counter status generation counter (calculated)

Wh

‒

1

‒

‒

GnMs.TotWhOutCalc

Parameter

Frequency monitoring lower minimum threshold

FrqCtl.Min

Lower minimum threshold grid frequency for frequency monitoring

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Lower minimum threshold

Hz

‒

0.01

InstallerSMA Grid GuardGridGuard.Cntry.FrqCtl.Min

Parameter

Frequency monitoring upper maximum threshold

FrqCtl.Max

Upper maximum threshold of grid frequency for frequency monitoring

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Upper maximum threshold

Hz

‒

0.01

InstallerSMA Grid GuardGridGuard.Cntry.FrqCtl.Max

Parameter

Frequency monitoring hysteresis minimum threshold

‒

Lower frequency difference for valid grid connection

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Hysteresis minimum threshold

0.00 Hz to 2.50 Hz

‒

0.01

InstallerSMA Grid GuardGridGuard.Cntry.FrqCtl.ReconMinDif

Parameter

Frequency monitoring hysteresis maximum threshold

‒

Upper frequency difference for valid grid connection

Installer

Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Hysteresis maximum threshold

0.00 Hz to 2.50 Hz

‒

0.01

InstallerSMA Grid GuardGridGuard.Cntry.FrqCtl.ReconMaxDif

Parameter

Nominal frequency

HzRtg

–

Installer

Grid Monitoring > Grid monitoring > Country standard > Nominal frequency

Hz

‒

0.01

InstallerSMA Grid GuardGridGuard.Cntry.HzRtg

Parameter

Grid monitoring time

‒

Minimum observation time for grid voltage and frequency in permissible range for connection

Installer

Grid Monitoring > Grid monitoring > Country standard > Waiting time until connection

1 s to 900 s

‒

1

InstallerSMA Grid GuardGridGuard.Cntry.VldTm

Parameter

Voltage monitoring upper minimum threshold

‒

Lower minimum threshold of grid voltage for voltage monitoring

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Lower minimum threshold

V

‒

0.01

InstallerSMA Grid GuardGridGuard.Cntry.VolCtl.Min

Parameter

Voltage monitoring upper maximum threshold

VolCtl.Max

Upper maximum threshold for grid voltage voltage monitoring

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Upper maximum threshold

V

‒

0.01

InstallerSMA Grid GuardGridGuard.Cntry.VolCtl.Max

Parameter

Voltage monitoring hysteresis minimum threshold

‒

Lower voltage difference for valid grid connection

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Hysteresis minimum threshold

0.00 V to 20.00 V

‒

0.01

InstallerSMA Grid GuardGridGuard.Cntry.VolCtl.ReconMinDif

Parameter

Voltage monitoring hysteresis maximum threshold

‒

Upper voltage difference for valid grid connection

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Hysteresis maximum threshold

0.00 V to 12.00 V

‒

0.01

InstallerSMA Grid GuardGridGuard.Cntry.VolCtl.ReconMaxDif

Parameter

Voltage increase protection

VolCtl.Rpro

‒

Installer

Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Voltage increase protection

253.00 V to 264.50 V

‒

0.01

InstallerSMA Grid GuardGridGuard.Cntry.VolCtl.Rpro

Measured value

Grid voltage phase L1

GridMs.PhV.phsA

Line voltage of the Sunny Island at line conductor L1

User

AC Side > Grid measurements > Phase voltage > Phase L1

V

‒

0.01

‒

‒

GridMs.PhV.phsA

Measured value

Grid voltage phase L2

GridMs.PhV.phsB

Netzspannung des Sunny Island an Phase L2 (Slave 1)

User

AC Side > Grid measurements > Phase voltage > Phase L2

V

‒

0.01

‒

‒

GridMs.PhV.phsB

Measured value

Grid voltage phase L3

GridMs.PhV.phsC

Line voltage of the Sunny Island at line conductor L3 (Slave 2)

User

AC Side > Grid measurements > Phase voltage > Phase L3

V

‒

0.01

‒

‒

GridMs.PhV.phsC

Measured value

Grid current phase L1

GridMs.A.phsA

Grid current of the Sunny Island at line conductor L1

User

AC Side > Grid measurements > Phase currents > Phase L1

A

‒

0.001

‒

‒

GridMs.A.phsA

Measured value

Grid current phase L2

GridMs.A.phsB

Grid current of the Sunny Island at line conductor L2 (Slave 1)

User

AC Side > Grid measurements > Phase currents > Phase L2

A

‒

0.001

‒

‒

GridMs.A.phsB

Measured value

Grid current phase L3

GridMs.A.phsC

Grid current of the Sunny Island at line conductor L3 (Slave 2)

User

AC Side > Grid measurements > Phase currents > Phase L3

A

‒

0.001

‒

‒

GridMs.A.phsC

Measured value

Grid frequency

GridMs.Hz

Grid frequency of the Sunny Island

User

AC Side > Grid measurements > Grid frequency

Hz

‒

0.01

‒

‒

GridMs.Hz

Measured value

Reactive power

GridMs.TotVAr

Total reactive power of Sunny Island inverters in a cluster

User

AC Side > Grid measurements > Reactive power

VAr

‒

1

‒

‒

GridMs.TotVAr

Measured value

Power

Pac

Total active power of Sunny Island inverters in a cluster

User

AC Side > Grid measurements > Power

W

‒

1

‒

‒

GridMs.TotW

Measured value

Reactive power L1

GridMs.VAr.phsA

Reactive power of the Sunny Island at line conductor L1

User

AC Side > Grid measurements > Reactive power > Phase L1

VAr

‒

1

‒

‒

GridMs.VAr.phsA

Measured value

Reactive power L2

GridMs.VAr.phsB

Reactive power of the Sunny Island at line conductor L2 (Slave 1)

User

AC Side > Grid measurements > Reactive power > Phase L2

VAr

‒

1

‒

‒

GridMs.VAr.phsB

Measured value

Reactive power L3

GridMs.VAr.phsC

Reactive power of the Sunny Island at line conductor L3 (Slave 2)

User

AC Side > Grid measurements > Reactive power > Phase L3

VAr

‒

1

‒

‒

GridMs.VAr.phsC

Measured value

Power L1

GridMs.W.phsA

Active power of the Sunny Island at line conductor L1

User

AC Side > Grid measurements > Power per phase > Phase L1

W

‒

1

‒

‒

GridMs.W.phsA

Measured value

Power L2

GridMs.W.phsB

Active power of the Sunny Island at line conductor L2 (Slave 1)

User

AC Side > Grid measurements > Power per phase > Phase L2

W

‒

1

‒

‒

GridMs.W.phsB

Measured value

Power L3

GridMs.W.phsC

Active power of the Sunny Island at line conductor L3 (Slave 2)

User

AC Side > Grid measurements > Power per phase > Phase L3

W

‒

1

‒

‒

GridMs.W.phsC

Measured value

Charge current limitation

‒

‒

Installer

Device > Inverter > Charge current limitation

A

‒

0.01

‒

‒

Inverter.AcChaA

Measured value

Discharge current limitation

‒

‒

Installer

Device > Inverter > Discharge current limitation

A

‒

0.01

‒

‒

Inverter.AcDschA

Parameter

Maximum AC battery charge current

‒

Maximum AC current during charging and discharging in A: The actual AC current can be limited due to normative requirements.

Installer

Device > Inverter > Maximum AC charge current

A

‒

0.001

Installer

‒

Inverter.AcChaAMax

Parameter

Extension cluster address

‒

‒

Installer

Device > Inverter > Cluster > Address

1 to 11

‒

1

Installer

‒

Inverter.Clt.Addr

Parameter

Serial number device 1

‒

‒

Installer

Device > Inverter > Cluster > Serial No. device 1

0 to 4294967294

‒

1

Installer

‒

Inverter.Clt.SerNumDev1

Parameter

Serial number device 2

‒

‒

Installer

Device > Inverter > Cluster > Serial No. device 2

0 to 4294967294

‒

1

Installer

‒

Inverter.Clt.SerNumDev2

Parameter

Frequency droop P(f)

‒

‒

Installer

Device > Inverter > Frequency droop P(f)

−1 Hz/kW to +1 Hz/kW

‒

0.001

Installer

‒

Inverter.FrqDrp

Parameter

Inverter nominal frequency

‒

Nominal frequency of the Sunny Island

Installer

Device > Inverter > Nominal frequency

Hz

‒

1

Installer

‒

Inverter.HzRtg

Parameter

cosPhi setpoint, cosPhi config., direct specif.

PF-PF

–

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi, direct specification > cosPhi specification

0.80 to 1.00

‒

0.01

InstallerSMA Grid GuardInverter.VArModCfg.PFCnstCfg.PF

Parameter

cosPhi at start point, cosPhi(P) char. config.

PF-PFStr

–

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > cosPhi of start point

0.80 to 1.00

‒

0.01

InstallerSMA Grid GuardInverter.VArModCfg.PFCtlWCfg.PFStr

Parameter

cosPhi at end point, cosPhi(P) char. config.

PF-PFStop

–

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > cosPhi of end point

0.80 to 1.00

‒

0.01

InstallerSMA Grid GuardInverter.VArModCfg.PFCtlWCfg.PFStop

Parameter

Act. power at end point, cosPhi(P) char. config.

PF-WNomStop

–

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Active power at end point

%

‒

1

InstallerSMA Grid GuardInverter.VArModCfg.PFCtlWCfg.WNomStop

Parameter

Act. power at start point, cosPhi(P) char. config.

PF-WNomStr

–

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Active power at starting point

%

‒

1

InstallerSMA Grid GuardInverter.VArModCfg.PFCtlWCfg.WNomStr

Parameter

Reactive power setpoint

‒

‒

Installer

System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power mode of PV system control > Reactive power setpoint

VAr

‒

1

InstallerDevice Control ObjectInverter.VArModCfg.VArCtlComCfg.VArSpt

Parameter

Inverter nominal voltage

‒

Nominal voltage of the Sunny Island

Installer

Device > Inverter > Nominal voltage

V

‒

1

Installer

‒

Inverter.VRtg

Parameter

Voltage droop Q (U)

‒

‒

Installer

Device > Inverter > Voltage droop Q (U)

−8 V/kVAr to +8 V/kVAr

‒

0.001

Installer

‒

Inverter.VtgDrp

Parameter

Difference between starting frequency and grid frequency, linear instantaneous power gradient configuration

P-HzStr

This value defines how many Hz above the nominal frequency of the inverter the active power limitation starts.

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Difference between starting freq. and grid freq.

0.00 Hz to 5.00 Hz

‒

0.01

InstallerSMA Grid GuardInverter.WCtlHzModCfg.WCtlHzCfg.HzStr

Parameter

Difference between reset frequency and grid frequency, linear instantaneous power gradient configuration

P-HzStop

This value defines how many Hz above the nominal frequency of the inverter the active power limitation stops.

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Difference between reset frequency and grid freq.

0.00 Hz to 5.00 Hz

‒

0.01

InstallerSMA Grid GuardInverter.WCtlHzModCfg.WCtlHzCfg.HzStop

Parameter

Active power gradient, linear instantaneous power gradient configuration

P-WGra

–

Installer

System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Active power gradient

10 % to 130 %

‒

1

InstallerSMA Grid GuardInverter.WCtlHzModCfg.WCtlHzCfg.WGra

Parameter

Reconnect gradient after grid fault

WGraRecon

Power gradient after a grid error

Installer

System and device control > Inverter > Power gradient for reconnection after grid fault

1 % to 100 %

‒

1

InstallerSMA Grid GuardInverter.WGraRecon

Parameter

Maximum active power device

Plimit

‒

User

Device > Inverter > Maximum active power

0 W to 20000 W

‒

1

‒

‒

Inverter.WLim

Parameter

Set active power limit

Pmax

‒

Installer

Device > Inverter > Currently set active power limit

0 W to 5000 W

‒

1

Installer

‒

Inverter.WMax

Parameter

Active power setpoint

‒

Limitation of active power feed-in at the indicated measuring point

Installer

System and device control > Inverter > Configuration of feed-in management > Configuration of active power mode of PV system ctrl > Active power setpoint

W

‒

1

InstallerDevice Control ObjectInverter.WModCfg.WCtlComCfg.WSpt

Parameter

Lmt value battery state of charge for start load shedding 1

‒

Battery state of charge limit for start of load shedding 1 in standard time period: This is the valid threshold without the additional time period.

Installer

Device > Load shedding 1 > Limit of battery state of charge for start

%

‒

1

Installer

‒

LodShd1.ChaStrLim

Parameter

Lmt value battery state of charge for stop load shedding 1

‒

Battery state of charge limit for end of load shedding 1 in standard time period: This is the valid threshold without the additional time period.

Installer

Device > Load shedding 1 > Limit of battery state of charge for stop

%

‒

1

Installer

‒

LodShd1.ChaStopLim

Parameter

Start time additional time range load shedding 1

‒

–

Installer

Device > Load shedding 1 > Additional time range > Start time

0 to 86399

‒

1

Installer

‒

LodShd1.AddTm.StrTm

Parameter

Time load shedding 1

‒

Start time of the standard additional time period for load shedding 1; corresponds to the end time of the additional time period

Installer

Device > Load shedding 1 > Additional time range > End time

0 to 86399

‒

1

Installer

‒

LodShd1.AddTm.StopTm

Parameter

Limit battery state of charge for start load shedding 1 in add time range

‒

–

Installer

Device > Load shedding 1 > Additional time range > Limit of battery state of charge for start

%

‒

1

Installer

‒

LodShd1.AddTm.ChaStrLim

Parameter

Limit battery state of charge for stop load shedding 1 in add time range

‒

–

Installer

Device > Load shedding 1 > Additional time range > Limit of battery state of charge for stop

%

‒

1

Installer

‒

LodShd1.AddTm.ChaStopLim

Parameter

Lmt value battery state of charge for start load shedding 2

‒

Battery state of charge limit for start of load shedding 2 in standard time period: This is the valid threshold without the additional time period.

Installer

Device > Load shedding 2 > Limit of battery state of charge for start

%

‒

1

Installer

‒

LodShd2.ChaStrLim

Parameter

Lmt value battery state of charge for stop load shedding 2

‒

Battery state of charge limit for end of load shedding 2 in standard time period: This is the valid threshold without the additional time period.

Installer

Device > Load shedding 2 > Limit of battery state of charge for stop

%

‒

1

Installer

‒

LodShd2.ChaStopLim

Parameter

Start time additional time range load shedding 2

‒

Start time of the additional time period for load shedding 2; corresponds to the start time of the additional time period

Installer

Device > Load shedding 2 > Additional time range > Start time

0 to 86399

‒

1

Installer

‒

LodShd2.AddTm.StrTm

Parameter

Time load shedding 2

‒

Start time of the standard additional time period for load shedding 2; corresponds to the end time of the additional time period

Installer

Device > Load shedding 2 > Additional time range > End time

0 to 86399

‒

1

Installer

‒

LodShd2.AddTm.StopTm

Parameter

Limit battery state of charge for start load shedding 2 in add time range

‒

Battery state of charge limit for start of load shedding 2 in the standard additional time period

Installer

Device > Load shedding 2 > Additional time range > Limit of battery state of charge for start

%

‒

1

Installer

‒

LodShd2.AddTm.ChaStrLim

Parameter

Limit battery state of charge for stop load shedding 2 in add time range

‒

–

Installer

Device > Load shedding 2 > Additional time range > Limit of battery state of charge for stop

%

‒

1

Installer

‒

LodShd2.AddTm.ChaStopLim

Parameter

Modbus TCP server port

‒

‒

User

External Communication > Modbus > TCP server > Port

1 to 65535

502 

1

Installer

‒

Mb.TcpSrv.Port

Parameter

Modbus UDP server port

‒

‒

User

External Communication > Modbus > UDP server > Port

1 to 65535

502 

1

Installer

‒

Mb.UdpSrv.Port

Measured value

Meter reading consumption meter

‒

–

User

AC Side > Measured values > Consumption > Absorbed energy

Wh

‒

1

‒

‒

Metering.Csmp.TotWhIn

Measured value

Load power

‒

Total power of the loads

User

AC Side > Measured values > Consumption > Power absorbed

W

‒

1

‒

‒

Metering.Csmp.TotWIn

Measured value

Operating time energy count

‒

Energy meter run time for the energy consumed and supplied of the Sunny Island

Installer

AC Side > Measured values > Operating time energy count

s

‒

1

‒

‒

Metering.EnCntTm

Parameter

Speedwire meter serial no.

‒

‒

User

System communication > Measured values > Meter on Speedwire > Serial Number

0 to 4294967294

0 

1

User

‒

Metering.MsSpdwr.SerNumEN

Measured value

Power outage

‒

–

User

AC Side > Measured values > Power outage

s

‒

1

‒

‒

Metering.GriFailTms

Measured value

Energy absorbed today

‒

–

User

AC Side > Measured values > Grid measurements > Energy absorbed today

Wh

‒

1

‒

‒

Metering.GridMs.DyWhIn

Measured value

Energy fed into grid (today)

‒

Today's grid feed-in in kWh

User

AC Side > Measured values > Grid measurements > Daily yield

Wh

‒

1

‒

‒

Metering.GridMs.DyWhOut

Measured value

Power grid feed-in

‒

Power fed into the utility grid

User

AC Side > Measured values > Grid measurements > Supplied power

W

‒

1

‒

‒

Metering.GridMs.TotWOut

Measured value

Power grid reference

‒

Power drawn from the electricity grid

User

AC Side > Measured values > Grid measurements > Power absorbed

W

‒

1

‒

‒

Metering.GridMs.TotWIn

Measured value

Grid feed-in counter reading

GM.TotWhOut

–

User

AC Side > Measured values > Grid measurements > Total yield

Wh

‒

1

‒

‒

Metering.GridMs.TotWhOut

Measured value

Grid reference counter reading

‒

–

User

AC Side > Measured values > Grid measurements > Absorbed energy

Wh

‒

1

‒

‒

Metering.GridMs.TotWhIn

Parameter

Set offset of the supplied energy

‒

‒

User

AC Side > Measured values > Grid measurements > Set offset of the supplied energy

−4000000 kWh to +4000000 kWh

0 kWh

1

User

‒

Metering.GridMs.TotkWhOutOfs

Parameter

Set offset of the absorbed energy

‒

‒

User

AC Side > Measured values > Grid measurements > Set offset of the absorbed energy

−4000000 kWh to +4000000 kWh

0 kWh

1

User

‒

Metering.GridMs.TotkWhInOfs

Parameter

Usable meters on Speedwire

‒

‒

User

System communication > Measured values > Meter on Speedwire > Serial numbers for usable meters

0 to 4294967294

0 

1

‒

‒

Metering.MsSpdwr.UsSerNumEN

Measured value

Total output current of solar charger

‒

Total output current of all charge controllers

Installer

DC Side > Measured values > Solar charger > Current

A

‒

0.001

‒

‒

Metering.PvChaMs.Amp

Measured value

Total energy of photovoltaics current day

‒

This is the total energy of all charge controllers for the current day.

User

DC Side > Measured values > Solar charger > Daily energy photovoltaics

Wh

‒

1

‒

‒

Metering.PvChaMs.DyWhPv

Measured value

Power of the SI charger |s0|

‒

PV power of charge controller 4

Installer

DC Side > Measured values > Solar charger > Power of the SI charger |s0|

W

‒

1

‒

‒

Metering.PvChaMs.SiChaPvPwr

Measured value

Total energy of photovoltaics

‒

Total PV energy: This is the total energy of all charge controllers.

User

DC Side > Measured values > Solar charger > Total energy photovoltaics

Wh

‒

1

‒

‒

Metering.PvChaMs.TotWhPv

Measured value

Photovoltaic energy in solar charger

‒

Energy consumed by the Sunny Island inverter

Installer

DC Side > Measured values > Solar charger > Solar charger total energy

Wh

‒

1

‒

‒

Metering.PvChaMs.TotWhSICha

Measured value

Output of photovoltaics

‒

Gesamte PV-Leistung aller Laderegler

User

DC Side > Measured values > Solar charger > Output of photovoltaics

W

‒

1

‒

‒

Metering.PvChaMs.TotWPv

Measured value

PV power generated

‒

Power PV generation

User

AC Side > Measured values > PV system measurements > Supplied power

W

‒

1

‒

‒

Metering.PvMs.TotWOut

Measured value

PV generation counter reading

‒

–

User

AC Side > Measured values > PV system measurements > Total yield

Wh

‒

1

‒

‒

Metering.PvMs.TotWhOut

Measured value

Rise in self-consumption

‒

Total increased self-consumption

User

AC Side > Measured values > Self-consumption > Internal consumption increase

Wh

‒

1

‒

‒

Metering.SelfCsmp.AbsSelfCsmpInc

Measured value

Rise in self-consumption today

‒

Today's increased self-consumption

User

AC Side > Measured values > Self-consumption > Rise in self-consumption today

Wh

‒

1

‒

‒

Metering.SelfCsmp.DySelfCsmpInc

Measured value

Energy consumed internally

‒

–

User

AC Side > Measured values > Self-consumption > Energy consumed internally

Wh

‒

1

‒

‒

Metering.SelfCsmp.SelfCsmpWh

Measured value

Current rise in self-consumption

‒

Current increased self-consumption

User

AC Side > Measured values > Self-consumption > Current rise in self-consumption

W

‒

1

‒

‒

Metering.SelfCsmp.SelfCsmpInc

Measured value

Absorbed energy

‒

‒

User

AC Side > Measured values > Absorbed energy

Wh

‒

1

‒

‒

Metering.TotWhIn

Measured value

Total yield

E-Total

Energy supplied by the Sunny Island inverter

User

AC Side > Measured values > Total yield

Wh

‒

1

‒

‒

Metering.TotWhOut

Measured value

Absorbed energy

‒

‒

User

AC Side > Measured values > Absorbed energy

Wh

‒

1

‒

‒

Metering.WhIn

Measured value

Released energy

‒

‒

User

AC Side > Measured values > Energy released

Wh

‒

1

‒

‒

Metering.WhOut

Measured value

Total current multi-cluster discharging power

‒

Total active power currently supplied in the multicluster system

Installer

AC Side > Multi-cluster > Supplied power

kW

‒

1

‒

‒

MltClt.TotWOut

Parameter

Temp lmt for multifunct. relay with batt comp fan

‒

–

Installer

Device > Multifunction relay > Temperature limit for battery compartment fan

°C

‒

0.100000

Installer

‒

MltFncSw.BatFanTmp

Parameter

Start date of relay control for timer

‒

Start date timer 2

User

Device > Multifunction relay > Timer > Start date

dd,MM,yyyy HH:mm:ss

0,00,0000 00:00:00

1

User

‒

MltFncSw.Tmr.TmCtlStr

Parameter

Duration for which multifunction relay is activated for timer

‒

Duration for which the multifunction relay remains activated for timer 2

User

Device > Multifunction relay > Timer > Duration in which the relay is activated for timer

0 s to 359940 s

‒

1

User

‒

MltFncSw.Tmr.TmCtlOn

Parameter

Firmware version of the communication assembly

KP.swRev

‒

Installer

Device Components > Type Label > Communication assembly > Software version

0 to 4294967294

0 

1

‒

‒

Nameplate.CmpCom.SwRev

Parameter

Hardware version of the communication assembly

KP.hwRev

‒

Installer

Device Components > Type Label > Communication assembly > Hardware version

0 to 4294967294

0 

1

‒

‒

Nameplate.CmpCom.HwRev

Parameter

Revision status of the communication assembly

KP.RevVer

‒

Installer

Device Components > Type Label > Communication assembly > Revision status

0 to 255

0 

1

‒

‒

Nameplate.CmpCom.Rev

Parameter

Serial number of the communication assembly

‒

‒

Installer

Device Components > Type Label > Communication assembly > Serial number

0 to 4294967294

0 

1

‒

‒

Nameplate.CmpCom.SerNum

Parameter

SUSyID of the communication assembly

‒

‒

Installer

Device Components > Type Label > Communication assembly > SUSyID

0 to 4294967294

0 

1

‒

‒

Nameplate.CmpCom.SusyId

Parameter

Serial number of the main processor

CmpMain.SerNum

–

Installer

Device Components > Type Label > Main processor > Serial number

0 to 4294967294

0 

1

‒

‒

Nameplate.CmpMain.SerNum

Parameter

Firmware version of the main processor

HP.swRev

‒

User

Device Components > Type Label > Main processor > Software version

0 to 4294967294

0 

1

‒

‒

Nameplate.CmpMain.SwRev

Parameter

SUSyID of the main processor

CmpMain.SusyId

‒

Installer

Device Components > Type Label > Main processor > SUSyID

0 to 4294967294

0 

1

‒

‒

Nameplate.CmpMain.SusyId

Parameter

Firmware version of the logic component

CPLD.swRev

‒

Installer

Device Components > Type Label > Logic component > Software version

0 to 4294967294

0 

1

‒

‒

Nameplate.CmpSigProc.SwRev

Parameter

Firmware version of WLAN component

‒

‒

Installer

Device Components > Type Label > WLAN component > Software version

0 to 4294967294

0 

1

‒

‒

Nameplate.CmpWl.SwRev

Parameter

Communication version

ComRev

‒

Installer

Type Label > Type Label > Communication version

0 to 4294967294

0 

1

‒

‒

Nameplate.ComRev

Parameter

Software package

Pkg.swRev

‒

User

Type Label > Type Label > Software package

0 to 4294967294

0 

1

‒

‒

Nameplate.PkgRev

Parameter

Serial number

SerNumSet, Serial Number, SerialNumber

‒

User

Type Label > Type Label > Serial number

0 to 4294967294

0 

1

‒

‒

Nameplate.SerNum

Parameter

Serial no. Slave1 (Phase L2)

‒

–

Installer

Type Label > Type Label > Serial number > Slave 1

0 to 4294967294

‒

1

‒

‒

Nameplate.SerNum.Slv1

Parameter

Serial no. Slave2 (Phase L3)

‒

–

Installer

Type Label > Type Label > Serial number > Slave 2

0 to 4294967294

‒

1

‒

‒

Nameplate.SerNum.Slv2

Parameter

Cooling down time of generator

‒

–

User

Generator > Operation > Cooling time

0 s to 3600 s

‒

1

Installer

‒

Operation.CoolTm

Measured value

Number of events for user

Op.EvtCntUsr

‒

User

Status > Operation > Events for user

‒

‒

1

‒

‒

Operation.EvtCntUsr

Measured value

Number of events for installer

Op.EvtCntIstl

‒

Installer

Status > Operation > Events for installer

‒

‒

1

‒

‒

Operation.EvtCntIstl

Measured value

Current event number for manufacturer

Op.EvtNoDvlp

‒

User

Status > Operation > Current event > Event number manufacturer

‒

‒

1

‒

‒

Operation.Evt.EvtNo

Parameter

Max. start attempts after error

‒

Number of autostarts

Installer

Device > Operation > Maximum start attempts after error

0 to 10

‒

1

Installer

‒

Operation.FltRstrMaxCnt

Parameter

Idle period after generator fault

‒

–

User

Generator > Operation > Idle period after fault

0 s to 86400 s

‒

1

Installer

‒

Operation.FltStopTm

Measured value

Number of grid connections

Op.GriSwCnt

–

Installer

AC Side > Operation > N° grid conn. at grid conn.pt.

‒

‒

1

‒

‒

Operation.GriSwCnt

Measured value

Nominal power in Ok Mode

‒

‒

User

Status > Operation > Device status > Ok

W

‒

1

‒

‒

Operation.HealthStt.Ok

Measured value

Nominal power in Warning Mode

‒

‒

User

Status > Operation > Device status > Warning

W

‒

1

‒

‒

Operation.HealthStt.Wrn

Measured value

Nominal power in Fault Mode

‒

‒

User

Status > Operation > Device status > Fault

W

‒

1

‒

‒

Operation.HealthStt.Alm

Parameter

Generator nominal frequency

‒

–

User

Generator > Operation > Nominal frequency

Hz

‒

0.01

Installer

‒

Operation.HzRtg

Parameter

Average operating time of generator

‒

–

User

Generator > Operation > Min. operating time

0 s to 21600 s

‒

1

Installer

‒

Operation.MinRunTm

Parameter

Average idle period of generator

‒

Minimum stop time of the generator

User

Generator > Operation > Min. idle period

0 s to 21600 s

‒

1

Installer

‒

Operation.MinStopTm

Measured value

Waiting time until feed-in

Op.TmsRmg

(Remaining time of grid monitoring)

User

Status > Operation > Waiting time until feed-in

s

‒

1

‒

‒

Operation.RmgTms

Parameter

Operating time for time-controlled inverter op.

‒

–

User

Device > Operation > Time control > Operating time

0 s to 359940 s

‒

1

User

‒

Operation.TmCtl.ActTm

Parameter

Start date for time-controlled inverter operation

‒

–

User

Device > Operation > Time control > Start time

dd,MM,yyyy HH:mm:ss

0,00,0000 00:00:00

1

User

‒

Operation.TmCtl.StrTm

Measured value

Remaining min. operating time of generator

‒

–

Installer

Generator > Operation > Remaining min. operating time

s

‒

1

‒

‒

Operation.RmgMinRunTm

Parameter

Warm-up time of generator

‒

–

User

Generator > Operation > Warm-up time

5 s to 900 s

‒

1

Installer

‒

Operation.WrmTm

Parameter

Set active power limit at grid connection point

‒

‒

User

System and device control > Grid connection point > Currently set active power limit

0 W to 500000 W

‒

1

Installer

‒

PCC.WMax

Parameter

Maximum unsymmetric load

‒

‒

User

System and device control > Grid connection point

0 W to 2147483647 W

‒

1

User

‒

PCC.WMaxAsym

Parameter

Set active power limit at grid connection point

‒

‒

User

System and device control > Grid connection point > Set active power limit

0 % to 100 %

100 %

1

Installer

‒

PCC.WMaxNom

Parameter

Nominal PV system power

‒

‒

User

DC Side > PV system > Nominal power

0 W to 500000 W

2500 W

1

Installer

‒

Plnt.DcWRtg

Parameter

Battery state of charge for protection mode

‒

Battery state of charge for preservation mode level 1, 2 and 3

Installer

Battery > Protection mode > Limit of battery state of charge

0.0 % to 70.0 %

‒

0.1

Installer

‒

ProMod.ChaSttLim

Parameter

Start time of battery protection mode level

‒

Start time battery preservation mode level 2

Installer

Battery > Protection mode > Start time

0 to 86399

‒

1

Installer

‒

ProMod.StrTm

Parameter

End time of battery protection mode level

‒

End time of the battery-preservation mode 2

Installer

Battery > Protection mode > End time

0 to 86399

‒

1

Installer

‒

ProMod.StopTm

Parameter

Maximum current from public grid

‒

Maximum current from the utility grid

Installer

AC Side > Public electricity mains > Maximum current of the ext. network interface

A

‒

0.001

Installer

‒

PubGri.ExtGriAMax

Parameter

Maximum network reverse power

‒

–

Installer

AC Side > Public electricity mains > Power monitoring > Maximum reverse power

W

‒

1

Installer

‒

PubGri.PwrMon.RvPwrMax

Parameter

Maximum network reverse power tripping time

‒

Permissible time for maximum grid reverse power

Installer

AC Side > Public electricity mains > Power monitoring > Maximum reverse power tripping time

0 s to 60 s

‒

1

Installer

‒

PubGri.PwrMon.RvPwrMaxTms

Parameter

Lmt battery state of charge for connection to grid

‒

This is the valid threshold without the additional time period.

Installer

AC Side > Public electricity mains > Network request via battery state of charge > Switch-on limit in time range

%

‒

1

Installer

‒

PubGri.GriDmdBatCha.OnLim

Parameter

Lmt battery state of charge for disconnection from grid

‒

This is the valid threshold without the additional time period.

Installer

AC Side > Public electricity mains > Network request via battery state of charge > Switch-off limit in time range

%

‒

1

Installer

‒

PubGri.GriDmdBatCha.OffLim

Parameter

Start time additional time range grid request

‒

Start of additional time period for grid request

Installer

AC Side > Public electricity mains > Network request via battery state of charge > Additional time range > Start time

0 to 86399

‒

1

Installer

‒

PubGri.GriDmdBatCha.AddTm.StrTm

Parameter

Start interval for network request

‒

Start of standard additional time period for grid request

Installer

AC Side > Public electricity mains > Network request via battery state of charge > Additional time range > End time

0 to 86399

‒

1

Installer

‒

PubGri.GriDmdBatCha.AddTm.StopTm

Parameter

Limit battery state of charge for connect to grid in add time range

‒

–

Installer

AC Side > Public electricity mains > Network request via battery state of charge > Additional time range > Switch-on limit in time range

%

‒

1

Installer

‒

PubGri.GriDmdBatCha.AddTm.OnLim

Parameter

Limit battery state of charge for disconnect from grid in add time range

‒

–

Installer

AC Side > Public electricity mains > Network request via battery state of charge > Additional time range > Switch-off limit in time range

%

‒

1

Installer

‒

PubGri.GriDmdBatCha.AddTm.OffLim

Parameter

Network request switch-on power limit

‒

–

User

AC Side > Public electricity mains > Network request via power > Switch-on power

W

‒

1

Installer

‒

PubGri.GriDmdW.WOn

Parameter

Network request switch-off power limit

‒

–

User

AC Side > Public electricity mains > Network request via power > Switch-off power

W

‒

1

Installer

‒

PubGri.GriDmdW.WOff

Measured value

Charge current specification self-consumption

‒

‒

Installer

Energy management > Self-consumption > Phase currents > Battery charge

A

‒

0.1

‒

‒

SelfCsmp.A.BatChrg

Measured value

Discharge current specification self-consumption

‒

‒

Installer

Energy management > Self-consumption > Phase currents > Battery discharge

A

‒

0.1

‒

‒

SelfCsmp.A.BatDsch

Parameter

Maximum duration of energy saving mode

‒

–

Installer

AC Side > Energy saving mode > Maximum duration of energy saving mode

3600 s to 604800 s

‒

1

Installer

‒

SltMod.SltTrcChaTm

Parameter

Time until change-over to energy saving mode

‒

–

Installer

AC Side > Energy saving mode > Time until change-over to energy saving mode

3600 s to 172800 s

‒

1

Installer

‒

SltMod.TrcChaSltTm

Parameter

Version of communication Bootloader

‒

‒

Installer

Device > Software component > Communication Bootloader > Software version

0 to 4294967294

0 

1

‒

‒

SwCmp.CmpComBlt.SwRev

Parameter

Version of WebUI

‒

‒

Installer

Device > Software component > Version of WebUI > Software version

0 to 4294967294

0 

1

‒

‒

SwCmp.CmpWebUsrItf.SwRev

Parameter

Version of time zone database

‒

‒

Installer

Device > Software component > Time zone database > Software version

0 to 4294967293

0 

1

‒

‒

SwCmp.CmpTmZn.SwRev

Measured value

Signal strength of the selected network

‒

‒

User

System communication > WLAN > Signal strength of the selected network

%

‒

1

‒

‒

Wl.SigPwr