| Slave 1 | 3002558726 |
| Slave 2 | 3002558725 |
| Device name | SN: 3001203272 |
| Device class | Battery Inverter |
| Device type | Sunny Island 4.4M |
| Software package | 1.2.4.R |
| Serial number | 3002558728 |
| MAC address | 00:40:AD:A3:19:B9 |
| WLAN-MAC address | DC:EF:CA:B6:C1:CF |
| Communication version | 1.1.1.1 |
| Language | English |
| Fan test | ------- |
| Type | Three-phase |
| System | Single-cluster |
| Cluster type in multi-cluster | ------- |
| Address | 1 |
| Serial No. device 1 | 0 |
| Serial No. device 2 | 0 |
| Maximum active power | 3,300 W |
| Frequency droop P(f) | 0.000 Hz/kW |
| Voltage droop Q (U) | 0.000 V/kVAr |
| Maximum AC charge current | 14.300 A |
| Currently set active power limit | 0 W |
| Nominal voltage | 230 V |
| Nominal frequency | 50 Hz |
| Functions for grid/offgrid operation | Functions for offgrid operation |
| Nominal voltage and frequency | 230V_50Hz |
| System performance | ------- |
| Address | Master |
| AST type | SIAST50-48S-12 |
| Activated | No |
| Start time | Jan 1, 2011 12:00:00 AM |
| Operating time | 0 s |
| Repeat cycle | Once |
| Operating condition | ------- |
| Cluster behaviour when a device fails | Further operation |
| Reset operating data | ------- |
| Load parameter | ------- |
| Maximum start attempts after error | 3 |
| Initiate device restart | ------- |
| Automatic time synchronization | No |
| Standard/Daylight Saving Time conversion on | Yes |
| Current time is daylight savings time | No |
| Time zone | (UTC+01:00) Brussels, Copenhagen, Madrid, Paris |
| NTP server | ntp.sunny-portal.com |
| Start date [A] | Jan 1, 2011 12:00:00 AM |
| Start date [B] | Jan 1, 2011 12:00:00 AM |
| Duration in which the relay is activated for timer [A] | 0 s |
| Duration in which the relay is activated for timer [B] | 0 s |
| Repeat cycle for timer [A] | Once |
| Repeat cycle for timer [B] | Once |
| Mindestzeit für die Nutzung überschüssiger Energie | 10.00 min |
| Spannungsunterschied für die Nutzung überschüssiger Energie | 0.15 V |
| Operating mode [A] | Automatic generator request |
| Operating mode [B] | 1-stage load shedding |
| Operating mode slave 1 [A] | Off |
| Operating mode slave 1 [B] | Off |
| Operating mode slave 2 [A] | Off |
| Operating mode slave 2 [B] | Off |
| Temperature limit for battery compartment fan | 104.0 °F |
| Rise in self-consumption switched on | No |
| Software version | 2.2.1.R |
| Software version | 1.3.95.R |
| Software version | 1.1.1.R |
| Start time | 00:00:00 |
| End time | 00:00:00 |
| Limit of battery state of charge for start | 30 % |
| Limit of battery state of charge for stop | 50 % |
| Limit of battery state of charge for start | 30 % |
| Limit of battery state of charge for stop | 50 % |
| End time | 00:00:00 |
| Start time | 00:00:00 |
| Limit of battery state of charge for start | 30 % |
| Limit of battery state of charge for stop | 50 % |
| Limit of battery state of charge for start | 30 % |
| Limit of battery state of charge for stop | 50 % |
| Set user password | •••••••• |
| Set installer password | •••••••• |
| Nominal power | 500,000 W |
| Type of additional DC sources | AC sources and DC charge controllers |
| Phase assignment device 1 | ------- |
| Phase assignment device 2 | ------- |
| Phase assignment | Phase L1 |
| Set offset of the supplied energy | 0 kWh |
| Set offset of the absorbed energy | 0 kWh |
| Selection of mains exchange capacity measurement method | SMA Energy Meter |
| Grid creating generator | Generator |
| Grounding type | TN grid |
| Automatic frequency control | Off |
| Type of AC distribution | Multicluster Box 6 |
| Maximum reverse power | 100 W |
| Maximum reverse power tripping time | 10 s |
| Switch-on limit in time range | 40 % |
| Switch-off limit in time range | 80 % |
| End time | 00:00:00 |
| Start time | 00:00:00 |
| Activated | No |
| Switch-on limit in time range | 40 % |
| Switch-off limit in time range | 80 % |
| Charge type | Equalization charge |
| Activated | No |
| Switch-on power | 4,000 W |
| Switch-off power | 2,000 W |
| Manual control | ------- |
| Maximum current of the ext. network interface | 16.000 A |
| Feed-back permitted | No |
| Cut-off time until shutdown | 20.00 min |
| Activated | No |
| Time until change-over to energy saving mode | 3.00 h |
| Maximum duration of energy saving mode | 11.99 h |
| Start feed-in | 04:00:00 |
| Stop feed-in | 22:00:00 |
| Hysteresis minimum threshold | 2.00 Hz |
| Hysteresis maximum threshold | 2.00 Hz |
| Upper maximum threshold | 52.00 Hz |
| Lower minimum threshold | 47.00 Hz |
| Enable voltage increase protection | No |
| Upper maximum threshold | 264.50 V |
| Lower minimum threshold | 184.00 V |
| Hysteresis minimum threshold | 2.00 V |
| Hysteresis maximum threshold | 2.00 V |
| Voltage increase protection | 253.00 V |
| Waiting time until connection | 30 s |
| Anti-islanding sensitivity | Normal |
| Nominal frequency | 50.00 Hz |
| Country standard | Island mode |
| Set country standard | ------- |
| Nominal frequency | 50.00 Hz |
| Min. operating time | 15.00 min |
| Min. idle period | 15.00 min |
| Cooling time | 5.00 min |
| Idle period after fault | 1.00 h |
| Warm-up time | 5.00 min |
| Type of current limitation | Fixed limit value for current limitation |
| Sensitivity of generator failure detection | Normal |
| Lower minimum threshold | 44.00 Hz |
| Upper maximum threshold | 55.00 Hz |
| Hysteresis minimum threshold | 2.00 Hz |
| Hysteresis maximum threshold | 2.00 Hz |
| Acknowledge fault | ------- |
| Lower minimum threshold | 172.50 V |
| Upper maximum threshold | 264.50 V |
| Hysteresis minimum threshold | 10.00 V |
| Hysteresis maximum threshold | 10.00 V |
| Maximum reverse power | 0 W |
| Maximum reverse power tripping time | 30 s |
| Automatic start | On |
| Manual control | Automatic generator start |
| Nominal current | 18.000 A |
| Request | Automatic generator start |
| Current control mode | No |
| Switch-on limit in time range | 40 % |
| Switch-off limit in time range | 80 % |
| Start time | 00:00:00 |
| End time | 00:00:00 |
| Switch-on limit in time range | 50 % |
| Switch-off limit in time range | 80 % |
| Activated | Yes |
| Switch-off power | 800 W |
| Switch-on power | 3,000 W |
| Average time | 1.00 min |
| Charge type | Full and equalization charge |
| Reaction to digital input | Off |
| Activated | No |
| Start time | Jan 1, 2011 12:00:00 AM |
| Operating time | 0 s |
| Repeat cycle | daily |
| Manual equalization charge | ------- |
| Batteriestromsensor | ------- |
| Rated capacity | 32,736 Wh |
| Nominal capacity | 682 Ah |
| Type | Valve Regulated Lead Acid battery (VRLA) |
| Nominal voltage | 48 V |
| Current sensor type (60mV 50mV) | ------- |
| Current sensor gain | 100 A |
| Maximum temperature | 104.0 °F |
| Switch-on limit after overtemperature shutdown | 95.0 °F |
| Output resistance DC connection | 0 Ohm |
| Maximum charging current | 416.020 A |
| Time for boost charge | 2.00 h |
| Time for equalization charge | 10.00 h |
| Time for full charge | 5.00 h |
| Discharge cut-off voltage | 35.00 V |
| Maximum discharge current | 900.000 A |
| Cell charge nominal voltage for boost charge | 2.40 V |
| Cell charge nominal voltage for full charging | 2.45 V |
| Cell charge nominal voltage for equalization charge | 2.45 V |
| Cell charge nominal voltage for float charge | 2.25 V |
| Cycle time full charge | 336.00 h |
| Cycle time equalization charge | 4,319.99 h |
| Temperature compensation | 0.004 V/°C |
| Automatic equalization charge | On |
| Voltage setpoint with deactivated BMS | 54.00 V |
| Max. charge capacity | 9,900 W |
| Max. discharge capacity | 9,900 W |
| Process specification battery charge current | ------- |
| Process specification battery discharge current | ------- |
| Lower lmt deep disch. protect area prior shutdown | 10 % |
| Minimum width of deep discharge protection area | 5 % |
| Minimum width of backup power area | 0 % |
| Area width for conserving battery state of charge | 5 % |
| Minimum width of own consumption area | 35 % |
| Most profitable month | June profitable |
| Season operation active | Yes |
| Start time [A] | 22:00:00 |
| Start time [B] | 17:00:00 |
| End time [A] | 06:00:00 |
| End time [B] | 09:00:00 |
| Limit of battery state of charge [A] | 20.0 % |
| Limit of battery state of charge [B] | 15.0 % |
| Limit of battery state of charge [C] | 10.0 % |
| Serial Number | 0 |
| Serial numbers for usable meters [A] | ------- |
| Serial numbers for usable meters [B] | ------- |
| Serial numbers for usable meters [C] | ------- |
| Operating mode | Time-controlled |
| Time of the automatic update | 05:00:00 |
| Automatic configuration switched on | Yes |
| IP Address | 192.168.0.170 |
| Subnet mask | 255.255.255.0 |
| Gateway IP | 192.168.0.170 |
| DNS server IP | 192.168.0.170 |
| SSID | |
| Password | •••••••• |
| Encryption | WPA2-AES |
| Activated | Yes |
| Soft-access-point is turned on | Yes |
| Activate WPS | ------- |
| Automatic configuration switched on | Yes |
| IP Address | 192.168.0.173 |
| Subnet mask | 255.255.255.0 |
| Gateway IP | 192.168.0.173 |
| DNS server IP | 192.168.0.173 |
| Networks found [A] | SMA3002558726 |
| Networks found [B] | SMA3002558725 |
| Perform scan | ------- |
| Activated | No |
| Port | 502 |
| Activated | No |
| Port | 502 |
| Activated | Yes |
| Activation of communication test | ------- |
| Software version | 1.0.3.R |
| Serial number | 3001193684 |
| SUSyID | 358 |
| Software version | 1.2.3.R |
| Hardware version | R2 |
| Revision status | 0 |
| Serial number | 3001203272 |
| SUSyID | 371 |
| Software version | 0.0.12.R |
| Software version | 1.0.0.R |
| Design of the generation plant | Symmetric |
| cosPhi specification | 1.00 |
| Excitation type of cosPhi | Underexcited |
| Active power at starting point | 50 % |
| cosPhi of start point | 1.00 |
| Excitation type at starting point | Overexcited |
| Active power at end point | 100 % |
| cosPhi of end point | 0.90 |
| Excitation type at end point | Underexcited |
| Operating mode of static voltage stabilization | Off |
| Operating mode Active power | Act. power lim. via PV system ctrl |
| Difference between starting freq. and grid freq. | 0.20 Hz |
| Active power gradient | 40 % |
| Difference between reset frequency and grid freq. | 0.20 Hz |
| Operating mode active power red., overfreq. P(f) | Off |
| Source of ref. meas. for reactive/active power reduction | MC box |
| Phased reactive/act. power specification | ------- |
| Power gradient for reconnection after grid fault | 10 % |
| Curr. active power grad., reconnection, grid fault | On |
| Betriebsart Schieflastbegrenzung | Off |
| maximale Schieflast | 1,000,000 W |
| Operating mode of active power limitation | Off |
| Currently set active power limit | 500,000 W |
| Set active power limit | 100 % |
| Upper state of charge for reactivating feed-in | 70 % |
| Lower state of charge for locking feed-in | 60 % |